Drive control and features
49
The value of parameter 47.08 EXT PU SUPPLY or its source should be set to 1
(true) when a supply below 270 V DC – such as a battery – is used. In such a
configuration, an additional DC power supply (JPO-01) is needed to power the main
circuit electronics. With an AC supply, the value of parameter 47.08 EXT PU
SUPPLY or its source should be set to 0 (false).
Parameters 47.06…47.08 are effective only when the Low voltage mode is active, ie,
value of parameter 47.05 LOW VOLT MOD ENA (or its source) is 1 (true).
In the Low voltage mode, the default voltage control and trip levels as well as the
braking chopper operation levels (see sections Voltage control and trip limits and
Braking chopper elsewhere in this chapter) are changed as follows:
Different system configurations are detailed in ACSM1 System Engineering Manual
(3AFE68978297 [English]).
Note: The Low voltage mode is not available for frames E to G.
Level
Value of parameter 47.08 EXT PU SUPPLY
FALSE TRUE
Supply voltage range
200…240 V AC ±10%
270…324 V DC ±10%
*48…270 V DC ±10%
Overvoltage trip level Unaffected Unaffected
Overvoltage control level 47.07 LOW VOLT DC MAX 47.07 LOW VOLT DC MAX
Undervoltage control level 47.06 LOW VOLT DC MIN Disabled
Undervoltage trip level 47.06 LOW VOLT DC MIN - 50 V Disabled
Braking chopper activation
level
47.07 LOW VOLT DC MAX - 30 V 47.07 LOW VOLT DC MAX - 30 V
Braking chopper maximum
power level
47.07 LOW VOLT DC MAX + 30 V 47.07 LOW VOLT DC MAX + 30 V
*Requires additional DC power supply JPO-01