Advant
®
Controller 450 User’s Guide
Section 2.2.9 Bus Extension to S100 I/O
3BSE 002 415R701 Rev A 2-33
The status information is available:
On the Advant Controller 450 data base element for use in any application program.
On the Advant Controller system status display presented on central operator station
display screen.
Configuration, that is, defining the texts to be presented in the status displays, is performed in
the AC 450 data base element.
Functional Measures
Adjust all included communication modules designated CS513 (MasterBus 300,
MasterBus 300E) with respect to the actual configuration before a power switch on.
You are directed to set the following by jumpering:
Network number
Node number
Slave number
Protocol type.
For instructions, see the manual MasterNet Users Guide.
The data base elements in Advant Controller holding the corresponding data are
automatically updated at power-on/initialization.
Set the start mode selector on the CPU module front (PM511) in the CLEAR position.
Preparation for Start-up
Please see the general checklists in Section 2.2.15, Checklists.
Leave the battery for memory backup disconnected until the mains supply is switched on and
the application configuration is started. Otherwise, it will be discharged in a few hours.
2.2.9 Bus Extension to S100 I/O
You can use the following basic information when you install an electrical bus extension.
How to install an optical bus extension is described in S100 I/O Hardware Reference Manual.
Assembly
The different parts of the bus extension are mainly factory assembled. These include:
Bus master module which is included in PM511 in controller subrack
Slave boards DSBC 174 or DSBC 176, located in each I/O subrack (two per I/O subrack in
case of S100 I/O bus extension redundancy, only valid for DSBC 174)
Ribbon cables connecting subracks within a cabinet.
You are supposed to make the interconnection of the bus extension between cabinets.
Cabinets should be arranged side by side in a designated order. Ribbon cables with adapted
lengths are enclosed at delivery. The cables are marked with item designation at the connectors.

Table of Contents

Other manuals for ABB Advant Controller 450