Controller 450 User’s Guide
Chapter 2 Installation
2-88 3BSE 002 415R701 Rev A
Extension Off-line
1. Shut down the system by setting the start mode selector on the existing processor module
in STOP position. The display shows -3.
The entire process control is shut down!
2. Check module identities. If the existing module is withdrawn, insert again.
Keep the start mode selector in 2 (STOP) position.
3. Check module position 2 (item designation 108, see Appendix D, Item Designations) for
visible damage, dust, and so on.
4. Set start mode selector on the new processor module in 2 (STOP) position.
CAUTION
Do not forget the general rule: Reflect on the danger of ESD. Use the
grounded wristband when handling circuit boards.
5. Insert the new module in position 2.
There are alternative ways of continued installation with respect to safety.
Steps 6 - 9 describe a normal installation.
Steps 10 - 16 describe an installation with increased safety by checking basic changeover
functionality in working mode CONFIGURATION, without affecting the process
controlled.
------------ Normal Installation --------------------
6. Set the start mode selector on the existing processor module in 1 (AUTO) position.
Push the ENTER button. The display shows P1.
Process control starts.
7. Set the start mode selector on the new processor module in the same position as the
existing processor module.
8. Push the ENTER button on the new module.
Check the display. A correct installation gives the following indications in sequence:
a. b2 (UPGRADING), b1 STANDBY) after
<
90 sec.
b. LEDs DUAL on both processor modules light up.
9. It is recommended that you perform a function test. Manual changeover is described in
Chapter 5, Maintenance.
--------------------- end ----------------------------------
--------Installation with Increased Safety------
10. Set the start mode selector on the existing processor module in 1 (AUTO) position.
11. Connect an engineering station to the existing processor module and, after the connection
session, give the command ECONFIG. The display on the processor module front shows
P2 CONFIGURATION.

Table of Contents

Other manuals for ABB Advant Controller 450

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB Advant Controller 450 and is the answer not in the manual?

ABB Advant Controller 450 Specifications

General IconGeneral
BrandABB
ModelAdvant Controller 450
CategoryController
LanguageEnglish

Related product manuals