The load in an Advant Controller 450 caused by a central operator station or information
management station subscription is a linear function of the number of “objects” (for example,
AI, DI, PIDCON) subscribed for and of the update frequency. The load only comes up when a
subscription is utilized.
127(
The capacity of the communication bus must also be considered in the
performance calculation. See separate documentation attached the used bus.
Load data is given by a diagram, Figure 3-10. By extrapolation you may obtain the load figure
for an extended number of objects.
First an example and some general comments:
A display with 100 objects from one Advant Controller 450, with an update cycle of 3 sec,
generates a load of approximately 1% in the controller. Use of 7 different object types and
communication module CS513 with a slave CPU is presupposed.
Always present digital signals with event-controlled update in combination with 9 sec cyclic
update, for fast updating on changes while minimizing the load.
The total load in the controller from subscriptions for displays should normally not exceed
20%.

Table of Contents

Other manuals for ABB Advant Controller 450

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB Advant Controller 450 and is the answer not in the manual?

ABB Advant Controller 450 Specifications

General IconGeneral
BrandABB
ModelAdvant Controller 450
CategoryController
LanguageEnglish

Related product manuals