Significant engineering tool commands to use are:
1. DIsable Build Mode, DIBM PCx
2. DeBLock, DBL
NOTE
DIMPC must be performed to get update of I/O signals.
Indications of an operating system with a started application:
Analog inputs
A/D conversion in progress, LED C flashes (not all board types).
Analog outputs
Output signals are produced by the executing PC program.
Digital inputs
The LEDs on I/O board fronts show the process status regardless of whether or not the PC
program is executing.
Digital outputs
Output signals are produced by the executing PC program.
Indicated by LEDs on I/O board fronts.
2.4.2.8 Installation of Battery for Backup of Memory
The battery is mounted inside the cabinet on the right-hand side.
When the controller is started, connect the battery. Disconnectible connectors are found close to
the battery unit.
You know that the battery backup is functioning when you see the following indications:
On the Backup Power Supply SB510/SB511 front
by green LED IP indicating mains supply available and converter in operation.
by switch-off of the red LEDs F (Fault) and BF (Battery Fault).
Low ambient temperature may delay the switch off a few minutes.
the LED FC is turned on during some 10 hours, indicating fast charging.
On the Processor Module PM511 front
the green LED BC is turned on.
When you plan to disconnect power for a period of time exceeding four hours (two hours when
redundant processor modules are used), disconnect the battery. This avoids total discharge of the
battery.
Use the disconnectible contacts on the battery unit.
2.4.3 Peripheral Equipment
Only the printer is treated below.
For a description of the terminal MasterView 320, see the manual MasterView 320 User’s
Guide.

Table of Contents

Other manuals for ABB Advant Controller 450

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB Advant Controller 450 and is the answer not in the manual?

ABB Advant Controller 450 Specifications

General IconGeneral
BrandABB
ModelAdvant Controller 450
CategoryController
LanguageEnglish

Related product manuals