Advant
®
Controller 450 User’s Guide
Section 5.5.2 Diagnostics and Fault Announcement
3BSE 002 415R701 Rev A 5-13
Reference in Advant Cont roller 400 Display:
Presentation:
Function:
Actions at fault:
Block Diagram:
Program card 1.1
green
red cr
Supervision of program card including system software (check sum)
1. Install or replace program card (PCMCIA)
Plain System Message
at fault:
7
2. Replace processor module PM511
Software
System status OS
Program card 1.1
Hardware
DIAGN.
PM511
Program
card
configured
DB; PM511
SWE RR
Automatic
PROGRAM CARD Memory error/Missing card/Wrong card <pos.> Net xx Nod yy
yellow cr
Normal
Fault - wrong check sum or missing card
Warning - Initial check in progress
Reference in Advant Cont roller 400 Display:
Presentation:
Function:
Actions at fault:
Block Diagram:
Program card 3.1 (.2, 4.1)
Supervision of program card including system software (check sum)
1. Install or replace program card (PCMCIA)
Plain System Message
at fault:
8
2. Replace program card interface MB510
Software
System status OS
Program card 1.1
Hardware
DIAGN.
MB510
Program
card
configured
DB; MB510
ER R
Automatic
PROGRAM CARD Memory error/Missing card/Wrong card <pos.> Net xx Nod yy
green
red cr
yellow cr
Normal
Warning - Initial check in progress
Fault - wrong check sum or missing card

Table of Contents

Other manuals for ABB Advant Controller 450

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB Advant Controller 450 and is the answer not in the manual?

ABB Advant Controller 450 Specifications

General IconGeneral
BrandABB
ModelAdvant Controller 450
CategoryController
LanguageEnglish

Related product manuals