Page #511 background imageLoading...
Page #511 background image
Advant
®
Controller 450 User’s Guide
Section E.2 Calculation Algorithms and Forms with Technical Data
3BSE 002 415R701 Rev A E-3
Table E-2. Current Consumption and Power Dissipation, S100 I/O Boards
Type
Designation
Current Consump. (A)
Tot. Power
Dissipation (W)
Comments
No of
Boards
Total
I
tot
, P
tot
+5 V +24 V
DSAI 130 0.25 0.11 3.8
DSAI 130A 0.15 0.15 4.4 0.1 W/ch on connection unit
at 20 mA
DSAI 133 0.45 0.13 5.4
DSAI 133A 0.26 0.1 3.7 0.1 W/ch on connection unit
at 20 mA
DSAI 146 0.25 0.10 3.8
DSAI 155A 0.25 0.10 3.8
DSAO 110 0.30 0.53 14.0
DSAO 120 0.30 0.28 8.2
DSAO 120A 0.35 0.58 14
DSAO 130 0.30 0.22 8.6
DSAO 130A 0.25 0.54 11
DSAX 110 0.48 0.17 7.7
DSAX 110A - - - 0.1 W/ch on connection unit
at 20 mA
DSDC 111 1.40 0.10 12.0
DSDI 110A 0.46 - 5.5 With DSTD 150A, DSTD 190
DSDI 110A 0.46 8 mA/ch 12.0 With 4x DSTD 195
DSDI 110A 0.46 8 mA/ch 18.5 With 4x DSTD 198
DSDI 110A 0.46 - 7.5 With 4x DSTD 196
DSDI 110A 0.46 8 mA/ch 17.0 With 4x DSTD 197
DSDI 110A 0.46 8 mA/ch 18.5 With 4x DSTD 198
DSDI 110AV1 0.23 - 4.4 With DSTD 150A
DSTD 190V1
DSDI 110AV1 0.23 - 4.4 With 4x DSTD 195/
DSTD 196P/DSTD 197/
DSTD 198
DSDI 110AV1 0.23 - 4.4 With DSTD 145, DSTD 147,
DSTD 148
DSDI 120A 0.46 - 8.8
DSDI 120AV1 0.23 - 7.7

Table of Contents

Other manuals for ABB Advant Controller 450

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB Advant Controller 450 and is the answer not in the manual?

ABB Advant Controller 450 Specifications

General IconGeneral
BrandABB
ModelAdvant Controller 450
CategoryController
LanguageEnglish

Related product manuals