Advant
®
Controller 450 User’s Guide
Section I.3 List of System Messages and Corrective Actions
3BSE 002 415R701 Rev A I-5
Table I-6. Type 17, Code 1, 2, 3, 7, 8, 9 and 11
Type Code Significance Data 1 Data 2 Comments/Actions
17 1 Configuration error 21 Node number More than one node with the same node
number or MB 300, GCOM.
Change node number!
22 Network and
node number
AC400 node has different node numbers.
Set the same node number on all busses on
the node!
23 Network and
node number
The node is connected to more than one
control network.
Make sure that the node is connected to one
control network, i.e. that all network numbers
are within the same decade!
24 Network and
node number
MB 300, GCOM interface incompatible with
system software.
25 Network and
node number
Incorrect (duplicate) network number.
Change the network number to the correct
number!
50 H’LRSNCPSP
LR
SN
CP
SP
CS513 config. error
Logical Record in the data base
Slave Number
Carrier Position in the subrack
Submodule Position on the carrier
51 H’LRSNCPSP
LR
SN
CP
SP
CI532 config. error
Logical Record in the data base
Slave Number
Carrier Position in the subrack
Submodule Position on the carrier
52 H’LRSNCPSP
LR
SN
CP
SP
CI532 config. error. Position already used
Logical Record in the data base
Slave Number
Carrier Position in the subrack
Submodule Position on the carrier
11 1 12:23:44 17 1 CXNM540 H’00000000
Type 17 MasterNet
A21
11