Advant
®
Controller 450 User’s Guide
Appendix I System Messages
I-6 3BSE 002 415R701 Rev A
17 1 Configuration error 53 H’LRSNCPSP
LR
SN
CP
SP
Config. error
Logical Record in the data base
Slave Number
Carrier Position in the subrack
Submodule Position on the carrier
54 H’LRSNCPSP
LR
SN
CP
SP
The LAN channel is already used
Logical Record in the data base
Slave Number
Carrier Position in the subrack
Submodule Position on the carrier
2 Shortage of
resources
18 Network number Too many nodes connected to the network MB
300.
Reduce the number of nodes!
19 0=main processor
>0 = slave
processor
Incorrect allocation of memory at start-up.
3 Disconnection 11
2
3
Data link level disconnected
Faulty communication board or wiring
Faulty communication board
13
H’RRAANENO
RR
AA
NE
NO
Connection with node broken.
Faulty communication board or wiring.
Disconnection cause, 00 = no contact with
slave node.
Slave channel number. 00 = all channels.
Network number
Node number
7 Reconnected 13 H’0000NENO
NE
NO
Communication in working order
Network number
Node number
Table I-6. Type 17, Code 1, 2, 3, 7, 8, 9 and 11 (Continued)
Type Code Significance Data 1 Data 2 Comments/Actions

Table of Contents

Other manuals for ABB Advant Controller 450

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB Advant Controller 450 and is the answer not in the manual?

ABB Advant Controller 450 Specifications

General IconGeneral
BrandABB
ModelAdvant Controller 450
CategoryController
LanguageEnglish

Related product manuals