Advant
®
Controller 450 User’s Guide
Section 2.4.1 Safety Regulations
3BSE 002 415R701 Rev A 2-53
Necessary Outfit
The following kit is a minimum requirement:
• Ordinary hand tools.
• Universal instrument, for example a digital multimeter.
• Test leads with 4 mm banana contacts and reducer contacts for a 2 mm test jack.
• Necessary parts of the documentation listed in Section 1.4, Related Documentation.
• Specific documentation enclosed at delivery.
• Advant Station 100 Series Engineering Station.
2.4.1 Safety Regulations
The instructions given in Section 2.2.1, Safety Regulations are applicable in all situations when
you work with an Advant Controller and associated equipment. Please read the instructions
carefully. One instruction is highlighted:
DANGER
Work with care when supply voltage is applied in the system. The voltage in
the cabinet can cause injury and can even kill a human being.
2.4.2 Controller and I/O
Conditions given by “Setup”
If you finish the setup activities by using the checklists given in Section 2.2.15, Checklists,
the equipment is almost ready for start. Please read the following security information first.
Measures by Security Means
Power-up of a controller and I/O presents a small but real risk of spurious output signals to the
process due to a faulty hardware module.
Since this risk is very small, a general safe method, for example extraction of all output I/O
hardware during the first power-up, is not recommended. You are directed, however, to be
careful on a case-by-case basis.
Always identify and isolate critical process objects in some way if the process is energized.
Examples include:
• Opened safety switch.
• Disconnected power supply.
• Use of disconnectible terminal.
• Unplugged terminal block.
• Extracted output circuit board.
Perform succeeding operations after power-up, including necessary tests, carefully.