Advant
®
Controller 450 User’s Guide
Chapter 5 Maintenance
5-24 3BSE 002 415R701 Rev A
S100 I/O Redundant
Figure 5-5. System Status Display, S100 I/O Redundant Board
Stat Act Name
Stat Act
1
AXR1
AXR2
AXR3
Board 1 Board 2
Reference in S100 I/O Redundant Board Display:
Presentation:
Function :
Actions at fault :
Block Diagram:
User defined name
green filled Normal, the board is OK
red cr Fault - the board is erroneous
Status information for S100 I/O redundant boards
1. If stat indicates erroneous, the board should be replaced
Plain System Message
at fault :
1
(default DB: item designation for
Stat (Status)
the board)
green filled
The board is in service and primary
yellow cr
board is out of service
Act (Activated)
See Section 5.4.10.1 Board and Subrack Mounted Unit Exchange
2. If the boards are out of service, see respective data base item, terminal SERVICE
Software
DB; AX Redundant
System status
Hardware
ERR1
1/0
IMPL
DIAGN.
XX board 1
NAME
Stat
Act
´Name´
SERVICE
1/0Operator
dialog
DIAGN.
XX board 2
Act
Board 1
Board 2
Stat
yellow empty
The
board is in warning status
green empty The board is in service and backup
ERR2
ACT_BRD
1/2
station
S100 I/O bus ext ension HW
´Name´
PROC I/O ST
XX Board error Net xx Nod yy