Advant
®
Controller 450 User’s Guide
Chapter 5 Maintenance
5-64 3BSE 002 415R701 Rev A
DSDO 115 On-line replacement possible
Note! In general, the electrical connections between
output boards and the process is to be broken before the
board is extracted.
Alternative methods includes:
- Open terminal switches on the connection unit
- Disconnect cable which joins the board and
the connection unit
- Switch off relevant field power supply
DSDO 115A On-line replacement possible
Note! In general, the electrical connections between
output boards and the process is to be broken before the
board is extracted.
Alternative methods includes:
- Open terminal switches on the connection unit
- Disconnect cable which joins the board and
the connection unit
- Switch off relevant field power supply
DSDO 120A On-line replacement possible
Note! In general, the electrical connections between
output boards and the process is to be broken before the
board is extracted.
Alternative methods includes:
- Open terminal switches on the connection unit
- Disconnect cable which joins the board and
the connection unit
- Switch off relevant field power supply
DSDP 140A On-line replacement possible
Table 5-2. Replacement Aspects of Individual Board Types, S100 I/O (Continued)
Board type - Jumpering Comments