Advant
®
Controller 450 User’s Guide
Appendix H Halt Codes
H-4 3BSE 002 415R701 Rev A
2C System with redundant processor modules only.
Indication on the backup module.
Internal error.
Replace the backup processor module.
32 System with redundant processor modules only.
Indication on the “new” primary at changeover.
Error in changeover. Unexpected status.
This means a serious shut down of a redundant
system. Further detailed information of the possible
reason of the halt is stored in the system. This
information is accessible by ABB experts only.
36 System with redundant processor modules only.
Indication on the “new” primary at changeover.
Error in changeover. Unexpected status
This means a serious shut down of a redundant
system. Further detailed information of the possible
reason of the halt is stored in the system. This
information is accessible by ABB experts only.
38 System with redundant processor modules only.
Indication on the backup module.
Internal error. System program in backup and
primary is not equal.
Restart with the same system program in both
processor modules.
40 System with redundant processor modules only.
Error when initializing the backup module.
Try again by depressing the ENTER button. If the
same error occurs, replace the backup module.
41 System with redundant processor modules only.
Indication on the backup module.
Error detected in the initial diagnostic test.
The RCU-chip on the backup module may be
malfunctioning.
Replace the backup module.
42 System with redundant processor modules only.
Indication on the backup module.
Internal error in the task-scheduler for the
backup module.
Replace the backup module.
43 System with redundant processor modules only.
Indication on the backup module.
Hardware error on the RCU-chip.
Replace the backup module.
44 System with redundant processor modules only.
Indication on the backup module.
Error in the communication between the backup
and primary modules.
Replace the backup module.
Table H-1. List of Halt Codes (Continued)
Halt
Code
Significance Corrective Actions

Table of Contents

Other manuals for ABB Advant Controller 450

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB Advant Controller 450 and is the answer not in the manual?

ABB Advant Controller 450 Specifications

General IconGeneral
BrandABB
ModelAdvant Controller 450
CategoryController
LanguageEnglish

Related product manuals