100
Communication
Example:
Task: The 5
th
data word of the telegram (index05) should be connected to AuxCtrlWord (7.03).
To do:AuxCtrlWord (7.03) is the default content of DsetXplus2Val2 (90.05). The corresponding index
configuration number of DsetXplus2Val2 (90.05) is 8. Therefore, the configuration has to be done using the
following values in the IP address (all values are in hex):
service
0x10
(write single)
class
0x91
(drive IO map function)
instance
0x01
(output)
attribute
5
(index05)
data
08 00
(2 char hex value)