188
Signal and parameter list
Signal / Parameter name
min.
max.
def.
unit
10.33 DI9Invert (invert digital input 9)
Inversion selection for digital input 9:
0 =
Direct only available with digital extension board
1 =
Inverted only available with digital extension board
Int. Scaling: 1 == 1 Type: C Volatile: N
Direct
Inverted
Direct
-
10.34 DI10Invert (invert digital input 10)
Inversion selection for digital input
10:
0 =
Direct only available with digital extension board
1 =
Inverted only available with digital extension board
Int. Scaling: 1 == 1 Type: C Volatile: N
Direct
Inverted
Direct
-
10.35 DI11Invert (invert digital input 11)
Inversion selection for digital input 11:
0 =
Direct only available with digital extension board
1 =
Inverted only available with digital extension board
Int. Scaling: 1 == 1 Type: C Volatile: N
Direct
Inverted
Direct
-
Group 11: Speed reference inputs
11.01 Unused
11.02 Ref1Mux (speed reference 1 selector/multiplexer)
Speed reference 1 selector:
0 =
Open switch for speed ref. 1 is fixed open
1 =
Close switch for speed ref 1 is fixed closed, default
2 =
DI1 1= switch is closed, speed ref 1 is active; 0 = switch is open, speed ref = 0
3 =
DI2 1= switch is closed, speed ref 1 is active; 0 = switch is open, speed ref = 0
4 =
DI3 1= switch is closed, speed ref 1 is active; 0 = switch is open, speed ref = 0
5 =
DI4 1= switch is closed, speed ref 1 is active; 0 = switch is open, speed ref = 0
6 =
DI5 1= switch is closed, speed ref 1 is active; 0 = switch is open, speed ref = 0
7 =
DI6 1= switch is closed, speed ref 1 is active; 0 = switch is open, speed ref = 0
8 =
DI7 1= switch is closed, speed ref 1 is active; 0 = switch is open, speed ref = 0
9 =
DI8 1= switch is closed, speed ref 1 is active; 0 = switch is open, speed ref = 0
10 =
DI9 1= switch is closed, speed ref 1 is active; 0 = switch is open, speed ref = 0; only
available with digital extension board
11=
DI10 1= switch is closed, speed ref 1 is active; 0 = switch is open, speed ref = 0; only
available with digital extension board
12 =
DI11 1= switch is closed, speed ref 1 is active; 0 = switch is open, speed ref = 0; only
available with digital extension board
13 =
MCW Bit11 1= switch is closed, speed ref 1 is active; 0 = switch is open, speed ref = 0;
MainCtrlWord (7.01) bit 11
14 =
MCW Bit12 1= switch is closed, speed ref 1 is active; 0 = switch is open, speed ref = 0;
MainCtrlWord (7.01) bit 12
15 =
MCW Bit13 1= switch is closed, speed ref 1 is active; 0 = switch is open, speed ref = 0;
MainCtrlWord (7.01) bit 13
16 =
MCW Bit14 1= switch is closed, speed ref 1 is active; 0 = switch is open, speed ref = 0;
MainCtrlWord (7.01) bit 14
17 =
MCW Bit15 1= switch is closed, speed ref 1 is active; 0 = switch is open, speed ref = 0;
MainCtrlWord (7.01) bit 15
Int. Scaling: 1 == 1 Type: C Volatile: N
Open
MCW Bit15
Close
-