139
Winder
3ADW000379R0501 DCS550 Manual e e
Hint: Winder Blocks, which write to Standard Firmware Parameters:
(Condition: WriteToSpeedChain [WSW Bit 2] == TRUE):
Block: Parameter: Comment:
DiameterAct: SpeedRefScale (23.16) Sign +/- via SpeedRefSign (WCW Bit 3)
PID Ctrl: SpeedCorr (23.04) Dancer Mode && 40.18 = 23.04 (Default for Dancer Macro)
AdaptSPC Kp: KpS (24.03) 62.13 = 24.03 (Default)
Add1: IndepTorqMaxSPC
(20.24) / (20.25) Tension Mode && 64.01 = 20.24 (Default for Tension Macros)
Add2: LoadComp (26.02) ! = Speed Mode && 64.08 = 26.02 (Default)
SpeedCorr (23.04) is written directly from the Winder Logic in Tension Mode:
TensionOn (WSW Bit 8) == TRUE -> 23.04 = 61.14 [Sign +/- via TopBottom (WCW Bit 4)]
TensionOn (WSW Bit 8) == FALSE -> 23.04 = 0 (falling edge)
Winder macros
Winder macros are pre-programmed parameter sets. During start-up, configure the winder easily without
changing individual parameters. The functions of inputs, outputs and control structure are macro dependent.
Any winder macro can be adapted by changing individual parameters without restrictions. Select a winder
macro by means of WinderMacro (61.01). The following tables and diagrams show the structure of the
macros.
NotUsed
Winder is blocked, default setting. Following parameters are set when using WinderMacro (61.01) = NotUsed: