Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
1.22 Mot1TempMeas (motor measured temperature)
Motor measured temperature. Used for motor overtemperature protection:
Unit depends on setting of M1TempSel (31.05):
NotUsed
reserved
PTC Ω
Int. Scaling: 1 == 1 Ω / 1 Type: I Volatile: Y
/ -
1.24 BridgeTemp (actual bridge temperature)
Actual bridge temperature in degree centigrade.
Int. Scaling: 1 == 1 °C Type: I Volatile: Y
1.25 CtrlMode (control mode)
Used control mode:
see TorqSel (26.01)
NotUsed
SpeedCtrl speed control
TorqCtrl torque control
CurCtrl current control
Int. Scaling: 1 == 1 Type: C Volatile: Y
1.29 Mot1FldCurRel (relative actual field current)
Relative field current in percent of
M1NomFldCur (99.11).
Int. Scaling: 100 == 1 % Type: SI Volatile: Y
1.30 Mot1FldCur (actual field current)
Field curren
t filtered with 500 ms.
Int. Scaling: 10 == 1 A Type: SI Volatile: Y
1.38 MainsFreqAct (internal mains frequency)
Calculated and internally controlled mains frequency. Output of PLL controller. See
also:
DevLimPLL (97.13)
KpPLL (97.14)
Int. Scaling: 100 == 1 Hz Type: I Volatile: Y
Group 2: Speed controller signals
2.01 SpeedRef2 (speed reference 2)
Speed reference after limiter:
M1SpeedMin (20.01)
M1SpeedMax (20.02)
Int. Scaling: (2.29) Type: SI Volatile: Y
2.02 SpeedRef3 (speed reference 3)
Speed reference after speed ramp and jog input.
Int. Scaling: (2.29) Type: SI Volatile: Y
n = speed actual - speed reference.
Int. Scaling: (2.29) Type: SI Volatile: Y
2.04 TorqPropRef (proportional part of torque reference)
P
-part of the speed controllers output in percent of MotNomTorque (4.23).
Int. Scaling: 100 == 1 % Type: SI Volatile: Y
2.05 TorqIntegRef (integral part of torque reference)
I
-part of the speed controllers output in percent of MotNomTorque (4.23).
Int. Scaling: 100 == 1 % Type: SI Volatile: Y
2.06 TorqDerRef (derivation part of torque reference)
D
-part of the speed controllers output in percent of MotNomTorque (4.23).
Int. Scaling: 100 == 1 % Type: SI Volatile: Y