Signal and parameter list 
3ADW000379R0501 DCS550 Manual e e 
24.28 TiS2 (2
nd
 i-part speed controller) 
2
nd
 integral time of the speed controller can be released by means of Par2Select (24.29). 
 
Int. Scaling:  1 == 1 ms  Type:  I  Volatile:  N 
24.29 Par2Select (selector for 2
nd
 set of speed controller parameters) 
Select active spe
ed controller parameters: 
ParSet1    parameter set 1 [KpS (24.03) and TiS (24.09)] is active, default 
 ParSet2    parameter set 2 [KpS2 (24.27) and TiS2 (24.28)] is active 
SpeedLevel  If |MotSpeed (1.04)| ≤ |SpeedLev (50.10)|, then parameter set1 is active. 
If |MotSpeed (1.04)| > |SpeedLev (50.10)|, then parameter set 2 is active. 
SpeedError  If |SpeedErrNeg (2.03)| ≤ |SpeedLev (50.10)|, then parameter set1 is active. 
If | SpeedErrNeg (2.03)| > |SpeedLev (50.10)|, then parameter set 2 is active. 
DI1    0 = parameter set 1 is active, 1 = parameter set 2 is active 
DI2    0 = parameter set 1 is active, 1 = parameter set 2 is active 
DI3    0 = parameter set 1 is active, 1 = parameter set 2 is active 
DI4    0 = parameter set 1 is active, 1 = parameter set 2 is active 
DI5    0 = parameter set 1 is active, 1 = parameter set 2 is active 
DI6    0 = parameter set 1 is active, 1 = parameter set 2 is active 
DI7    0 = parameter set 1 is active, 1 = parameter set 2 is active 
DI8    0 = parameter set 1 is active, 1 = parameter set 2 is active 
DI9    0 = parameter set 1 is active, 1 = parameter set 2 is active, only available with digital 
extension board 
DI10    0 = parameter set 1 is active, 1 = parameter set 2 is active, only available with digital 
extension board 
DI11    0 = parameter set 1 is active, 1 = parameter set 2 is active, only available with digital 
extension board 
MCW Bit11  0 = parameter set 1 is active, 1 = parameter set 2 is active, MainCtrlWord (7.01) bit 11 
MCW Bit12  0 = parameter set 1 is active, 1 = parameter set 2 is active, MainCtrlWord (7.01) bit 12 
MCW Bit13  0 = parameter set 1 is active, 1 = parameter set 2 is active, MainCtrlWord (7.01) bit 13 
MCW Bit14  0 = parameter set 1 is active, 1 = parameter set 2 is active, MainCtrlWord (7.01) bit 14 
MCW Bit15  0 = parameter set 1 is active, 1 = parameter set 2 is active, MainCtrlWord (7.01) bit 15 
 
Load and speed dependent adaptation parameters are valid regardless of the selected parameter set.
 
Int. Scaling:  1 == 1   Type:  C  Volatile:  N 
Group 25: Torque reference 
25.01 TorqRefA (torque reference A) 
External torque reference in percent of 
MotNomTorque (4.23). TorqRefA (25.01) can be scaled by LoadShare 
 
 
 is only valid, if TorqRefA Sel (25.10) = TorqRefA2501. 
Int. Scaling:  100 == 1 %  Type:  SI  Volatile:  Y 
25.03 LoadShare (load share) 
Scaling factor 
TorqRefA (25.01). 
Int. Scaling:  10 == 1 %  Type:  SI  Volatile:  N 
25.10 TorqRefA Sel (torque reference A selector) 
Selector for
 TorqRefExt (2.24): 
TorqRefA2501  TorqRefA (25.01), default 
AI1    analog input AI1 
AI2    analog input AI2 
AI3    analog input AI3 
AI4    analog input AI4 
AI5    analog input AI5 
AI6    analog input AI6 
Int. Scaling:  1 == 1   Type:  C  Volatile:  N