213
Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
24.28 TiS2 (2
nd
i-part speed controller)
2
nd
integral time of the speed controller can be released by means of Par2Select (24.29).
Int. Scaling: 1 == 1 ms Type: I Volatile: N
24.29 Par2Select (selector for 2
nd
set of speed controller parameters)
Select active spe
ed controller parameters:
ParSet1 parameter set 1 [KpS (24.03) and TiS (24.09)] is active, default
ParSet2 parameter set 2 [KpS2 (24.27) and TiS2 (24.28)] is active
SpeedLevel If |MotSpeed (1.04)| ≤ |SpeedLev (50.10)|, then parameter set1 is active.
If |MotSpeed (1.04)| > |SpeedLev (50.10)|, then parameter set 2 is active.
SpeedError If |SpeedErrNeg (2.03)| ≤ |SpeedLev (50.10)|, then parameter set1 is active.
If | SpeedErrNeg (2.03)| > |SpeedLev (50.10)|, then parameter set 2 is active.
DI1 0 = parameter set 1 is active, 1 = parameter set 2 is active
DI2 0 = parameter set 1 is active, 1 = parameter set 2 is active
DI3 0 = parameter set 1 is active, 1 = parameter set 2 is active
DI4 0 = parameter set 1 is active, 1 = parameter set 2 is active
DI5 0 = parameter set 1 is active, 1 = parameter set 2 is active
DI6 0 = parameter set 1 is active, 1 = parameter set 2 is active
DI7 0 = parameter set 1 is active, 1 = parameter set 2 is active
DI8 0 = parameter set 1 is active, 1 = parameter set 2 is active
DI9 0 = parameter set 1 is active, 1 = parameter set 2 is active, only available with digital
extension board
DI10 0 = parameter set 1 is active, 1 = parameter set 2 is active, only available with digital
extension board
DI11 0 = parameter set 1 is active, 1 = parameter set 2 is active, only available with digital
extension board
MCW Bit11 0 = parameter set 1 is active, 1 = parameter set 2 is active, MainCtrlWord (7.01) bit 11
MCW Bit12 0 = parameter set 1 is active, 1 = parameter set 2 is active, MainCtrlWord (7.01) bit 12
MCW Bit13 0 = parameter set 1 is active, 1 = parameter set 2 is active, MainCtrlWord (7.01) bit 13
MCW Bit14 0 = parameter set 1 is active, 1 = parameter set 2 is active, MainCtrlWord (7.01) bit 14
MCW Bit15 0 = parameter set 1 is active, 1 = parameter set 2 is active, MainCtrlWord (7.01) bit 15
Load and speed dependent adaptation parameters are valid regardless of the selected parameter set.
Int. Scaling: 1 == 1 Type: C Volatile: N
Group 25: Torque reference
25.01 TorqRefA (torque reference A)
External torque reference in percent of
MotNomTorque (4.23). TorqRefA (25.01) can be scaled by LoadShare
is only valid, if TorqRefA Sel (25.10) = TorqRefA2501.
Int. Scaling: 100 == 1 % Type: SI Volatile: Y
25.03 LoadShare (load share)
Scaling factor
TorqRefA (25.01).
Int. Scaling: 10 == 1 % Type: SI Volatile: N
25.10 TorqRefA Sel (torque reference A selector)
Selector for
TorqRefExt (2.24):
TorqRefA2501 TorqRefA (25.01), default
AI1 analog input AI1
AI2 analog input AI2
AI3 analog input AI3
AI4 analog input AI4
AI5 analog input AI5
AI6 analog input AI6
Int. Scaling: 1 == 1 Type: C Volatile: N