Electronic board details
3ADW000379R0501 DCS550 Manual e e
Terminal description
Connectors X1 to X5 provide the standard digital and analog connection of the drive.
Use connector X9 or slot1 for R-type extension I/O modules and R-type fieldbus adapters.
Use connector X11 or slot3 only for R-type extension I/O modules.
Connector X9 or slot1
Connector X11 or slot3
RAIO, RDIO
X
X
R-type fieldbus adapters
X
-
Connectors X12 and X13 connect the SDCS-CON-F to the SDCS-PIN-F for voltage, current and
temperature measurement. Additionally the firing pulses are sent to the thyristors trough the SDCS-PIN-F.
Use connector X33 to connect the DCS Control Panel either directly via a 40 mm jack plug or via a CAT
1:1 cable with RJ45 plugs.
Use connector X34 for firmware download, to connect DriveWindow Light, commissioning assistant and
DriveAP tool. Usually use the RS232 interface for parameter setting and commissioning the drive via
DriveWindow Light.
Use connector X37 to connect the SDCS-CON-F to the power supply from the SDCS-PIN-F.
A seven-segment display named H2500 is located on the control board SDCS-CON-F to show the state of
drive. It displays for example fault- and alarm codes. A detailed description of the seven-segment display is
available in chapter Status messages
.