Electronic board details 
3ADW000379R0501 DCS550 Manual e e 
Control board SDCS-CON-F 
Layout 
 
Location 
The SDCS-CON-F is mounted on an electronic tray. The electronic tray is put in the housing by means of four 
hinges and the SDCS-CON-F is connected with the SDCS-PIN-F through three flat cables. 
Memory circuit 
The SDCS-CON-F is equipped with a flash PROM that contains the firmware and the stored parameters. It is 
possible to handle the parameters by DCS Control Panel, DWL or overriding control. Changed parameters are 
stored immediately in the flash with the exception of parameters for cyclic communication via the dataset table 
in groups 90 to 92 and pointers in group 51. 
In addition, the fault logger entries are stored in the flash during de-energizing the auxiliary power. 
Watchdog function 
The SDCS-CON-F has an internal watchdog. The watchdog controls the proper function of the SDCS-CON-F 
and the firmware. If the watchdog trips, it has the following effects: 
−  the thyristor firing control is reset and disabled, 
−  all DI’s are forced low (zero) and 
−  all programmable AO’s are reset to zero (0 V). 
S1
1
2
3
S2
1
3
4
2
1
2
3
7
8
9
7
8
9
1
3
42
S3
7
8
S4
1
2
3
7
8
9
1
2
3
10
11
12
10
11
12
S5
1 3
4
2
1 3
4
2
10 11 12
S4
SDCS-CON-F
+24 V
X3:10
encoder supply
SDCS-
PIN-F
+5 V
4
5
6
4
5
6
1 3
4
2
1 3
4
2
*
6
5
7
8
6
5
*
*
*
*
7
8
9
*
*
*
*
**
*
BL_CONF_002_a.ai
X2X1 X3 X4 X5
1 1 1 1 1
S5
15
6 9
S3
S2
S4
1
2
1
2
1
2
1
2
D2100
1
D2001
D2002
D1000
1 30
1
2
1
2
S1
1 3
42
1
2
3
10
11
12
1 7
8
2
1
3
42
1
2
3
7
8
9
X12:
SDCS-PIN-F
X13:
SDCS-PIN-F
X34:
DriveWindow Light
X37:
SDCS-PIN-F
X9:
X11:
X33:
X300:
H2500:
 Slot 1
 Slot 3
 DCS Control Panel
Jumper coding
default value
250 Ω  x 20 mA = 5 V == 100 %
Jumper parking position;
normal DC tacho
Reserved, do not use
AITAC1+ (X1:4) connected to GND
Jumper parking position;
AITAC1+ (X1:4) notgrounded
Jumper parking position;
no PTC connected
PTC connected at X1:7-8, 4.75 kΩ
pull-up resistor activated
Encoder mode: differential; RC loads
activated with R = 121Ω and C = 100 nF
Encoder mode: single ended;
10 k
Ω
pull-up resistor acti vated
Encoder supply +5V,
sense at X3:8-9 is active
Encoder supply +24V,
no senseavailable
Firmware download
Normal program execution
or text download
do not change
AI1 (X1:5-6): R
in
 = 200 kΩ; range ±10V
AI1 (X1:5-6): R
in
 = 250Ω
∗∗
; range ±20 mA
AI2 (X1:7-8): R
in
 = 200 kΩ; range ±10V
AI2 (X1:7-8): R
in
 = 250Ω
∗∗
; range ±20 mA
Jumper parking position;
Reserved, do not use
fieldbus or
extension
extension
 routine test
 seven-
segment display
Jumpers shown in default position
I/O