63
Start-up
3ADW000379R0501 DCS550 Manual e e
Macros
Macros are pre-programmed parameter sets. During start-up, configure the drive easily without changing
individual parameters. The functions of inputs, outputs and control structure are macro dependent. Any macro
can be adapted by changing parameters without restrictions. Select macros by means of ApplRestore (99.07)
and ApplMacro (99.08) or the macro assistant in DWL. Check the result of the selection in MacroSel (8.10).
The following diagrams show the structure of the macros.
Macro name
Main
Contactor
ON / OFF
Start/Stop
DI function
Comment
E-stop ⇒ DI5
Reset ⇒ DI6
Standard
AC
Static
Jog1 ⇒ DI1
Jog2
⇒ DI2
ExtFault
⇒ DI3
ExtAlarm ⇒ DI4
Hardware I/O control
x
Man/Const
AC
Pulse
Jog1 ⇒
DI1
Jog2
⇒ DI2
Direction
⇒ DI3
SPC-KP, KI ⇒ DI4
Hardware I/O control;
select gain (KpS
⇔ Kps2,
TiS
⇔ TiS2)
x
Hand/Auto
AC
Static
Control ⇒ DI2
Speed reference
⇒ DI2
Direction ⇒ DI3
Hardware I/O or field bus
control
x
Hand/MotPot
AC
Pulse
Mot
PotUp
⇒
DI1
MotP
otDown ⇒ DI2
Direction
⇒ DI 3
Speed reference ⇒ DI4
Hardware I/O control;
reference: hardware or
MotPot
x
MotPot
AC
Static
Direction ⇒
DI1
MotPotUp
⇒ DI2
MotPotDown
⇒ DI3
MotPotMin ⇒ DI4
Hardware I/O control;
reference: MotPot
x
TorqCtrl
AC Static
OFF2 (C
oast stop)
⇒
DI1
Torq
Sel ⇒ DI2
ExtFault ⇒ DI3
Hardware I/O control; speed
control or torque reference
x
TorqLimit
AC
Static
Jog1 ⇒
DI1
Jog2
⇒ DI2
ExtFault
⇒ DI3
ExtAlarm ⇒ DI4
Hardware I/O control;
torque limit
x
2WreDCcontUS
DC
Static
Jog1 ⇒ DI1
Jog2
⇒ DI2
Ex
tFault ⇒ DI3
MainContAck ⇒ DI4
Hardware I/O control
x
3WreDCcontUS
DC
Pulse
Fix
edSpeed1
⇒
DI1
ExtFault
⇒ DI3
MainContAck ⇒ DI4
Hardware I/O control
x
3WreStandard
AC
Pulse
FixedSpeed1 ⇒
DI1
Ex
tFault ⇒ DI3
ExtAlarm ⇒ DI4
Hardware I/O control