Environmental Conditions
The technical data contain the technical specifications of the drive, e.g. the ratings, sizes and technical
requirements, provisions for fulfilling the requirements for CE and other markings and warranty policy.
Environmental limit values
230 to 525 V acc. to IEC 60038
Permissible cooling air temperature
±10 % continuous; ±15 % short-
time (0.5 to 30 cycles)
− with rated DC current (forced
ventilation):
− with different DC current see
figure below:
Static frequency deviation:
Dynamic: frequency range:
50 Hz: ±5 Hz; 60 Hz: ± 5 Hz
Relative humidity (at 5...+40°C):
5 to 95 %, no condensation
Note:
Special consideration must
be taken for voltage deviation in
Relative humidity (at 0...+5°C):
5 to 50 %, no condensation
Change of the ambient temp.
Converter modules and
options (line chokes, fuses,
field exciters, etc.):
Pollution degree (IEC 60664-1,
IEC 60439-1):
<1000 m above mean sea level:
100%, without current reduction
>1000 m above mean sea level:
with current reduction, see figure
below
Effect of the site elevation above sea level on the converter’s load
capacity:
Effect of the ambient temperature on the converter module load
capacity:
Current reduction to (%) for converter modules
Sound pressure level
LP (1 m distance)
Transport in
original Package
Short circuit withstand rating
The DCS
550 is suitable for use in a circuit
capable of delivering not more than:
1.5 mm, 2 - 9 Hz
0.5 g, 9
- 200 Hz
65 kA rms symmetrical ampere at a maximum
of 600 V
AC
66 - 70 dBA,
depending on fan