14
The DCS550
3ADW000379R0501 DCS550 Manual e e
Voltage and current ratings
The maximum available armature voltages have been calculated using the following assumptions:
− U
VN
= rated mains voltage, 3-phase,
− Voltage tolerance ±10 %,
− Internal voltage drop approximately 1 %
If a deviation or a voltage drop has to be taken into account in compliance with IEC and VDE standards, the
output voltage and / or the output current must be reduced.
The maximum available field voltage can be calculated using following formula:
+
∗∗≤
%100
%100
35.1
TOL
UU
VNF
, with:
U
F
= field voltage,
U
VN
= mains voltage and
TOL = tolerance of the mains voltage in %.
A
[A]
out
A
[A]
out
[V
AC
]
F
[A]
loss
[kW]
[m
3
/h]
voltage
-15 % / +10 %
AC
230 V
AC
,
230 V
DC
-15 % / +10 %
②
③
① Ratings for 500 V
AC
-10 %
② 900 A
DC
for 35°C and 850 A
DC
for 40°C ambient temperature
③ 1000 A
DC
for 35°C and 950 A
DC
for 40°C ambient temperature