223
Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
31.08 M1KlixonSel (klixon selector)
The drive trips with
F506 M1OverTemp [FaultWord1 (9.01) bit 5] if a digital input selected and the klixon is
NotUsed default
DI1 0 = fault, 1 = no fault
DI2 0 = fault, 1 = no fault
DI3 0 = fault, 1 = no fault
DI4 0 = fault, 1 = no fault
DI5 0 = fault, 1 = no fault
DI6 0 = fault, 1 = no fault
DI7 0 = fault, 1 = no fault
DI8 0 = fault, 1 = no fault
DI9 0 = fault, 1 = no fault. Only available with digital extension board
DI10 0 = fault, 1 = no fault. Only available with digital extension board
DI11 0 = fault, 1 = no fault. Only available with digital extension board
It is possible to connect several klixons in series.
Int. Scaling: 1 == 1 Type: C Volatile: N
31.10 M1LoadCurMax (maximum overload current I
2
T-function)
Maximum overload current of the connected motor in % of
M1NomCur (99.03). The overload current is
independent of its sign and applies to both current directions. Thus an activated I
2
T-function limits
and M1CurLimBrdg2 (20.13).
2
T-function is inactive, if M1LoadCurMax (31.10) is set to values ≤ 100 %. In case the I
2
T-function is
reducing the armature current
A108 MotCurReduce [AlarmWord1 (9.06) bit 7] is set.
The used current limit depends also on the converter's actual limitation situation (e.g. torque limits, other
current limits, field weakening).
Int. Scaling: 100 == 1 % Type: I Volatile: N
31.11 M1OvrLoadTime (overload time I
2
T-function)
Longest permissible time for the maximum overload current defined in
M1LoadCurMax (31.10).
2
T-protection is inactive, if M1OvrLoadTime (31.11) is set to zero. In case the I
2
T-protection is reducing
A108 MotCurReduce [AlarmWord1 (9.06) bit 7] is set.
Int. Scaling: 1 == 1 s Type: I Volatile: N
31.12 M1RecoveryTime (recovery time I
2
T-function)
Recovery time during which a reduced current must flow.
2
T-protection is inactive, if M1RecoveryTime (31.12) is set to zero. In case the I
2
T-protection is reducing
A108 MotCurReduce [AlarmWord1 (9.06) bit 7] is set.
Int. Scaling: 1 == 1 s Type: I Volatile: N
Group 34: DCS Control Panel display
Signal and parameter visualization on the DCS Control Panel:
Setting a display parameter to 0 results in no signal or parameter displayed.
Setting a display parameter from 101 to 9999 displays the belonging signal or parameter. If a signal or parameter does not
exist, the display shows “n.a.”.
34.01 DispParam1Sel (select signal / parameter to be displayed in the DCS Control Panel row 1)
Index pointer to the source of the DCS Control Panel first display row [e.g. 101 equals
MotSpeedFilt (1.01)].
Int. Scaling: 1 == 1 Type: I Volatile: N