Signal and parameter list 
3ADW000379R0501 DCS550 Manual e e 
31.08 M1KlixonSel (klixon selector) 
The drive trips with 
F506 M1OverTemp [FaultWord1 (9.01) bit 5] if a digital input selected and the klixon is 
 
NotUsed  default 
DI1  0 = fault, 1 = no fault 
DI2  0 = fault, 1 = no fault 
DI3  0 = fault, 1 = no fault 
DI4  0 = fault, 1 = no fault 
DI5  0 = fault, 1 = no fault 
DI6  0 = fault, 1 = no fault 
DI7  0 = fault, 1 = no fault 
DI8  0 = fault, 1 = no fault 
DI9  0 = fault, 1 = no fault. Only available with digital extension board 
DI10  0 = fault, 1 = no fault. Only available with digital extension board 
DI11  0 = fault, 1 = no fault. Only available with digital extension board 
 
It is possible to connect several klixons in series.
 
Int. Scaling:  1 == 1 Type:  C  Volatile:  N 
31.10 M1LoadCurMax (maximum overload current I
2
T-function) 
Maximum overload current of the connected motor in % of 
M1NomCur (99.03). The overload current is 
independent of its sign and applies to both current directions. Thus an activated I
2
T-function limits 
 and M1CurLimBrdg2 (20.13). 
2
T-function is inactive, if M1LoadCurMax (31.10) is set to values ≤ 100 %. In case the I
2
T-function is 
reducing the armature current 
A108 MotCurReduce [AlarmWord1 (9.06) bit 7] is set. 
 
  The used current limit depends also on the converter's actual limitation situation (e.g. torque limits, other 
current limits, field weakening). 
Int. Scaling:  100 == 1 %  Type:  I  Volatile:  N 
31.11 M1OvrLoadTime (overload time I
2
T-function) 
Longest permissible time for the maximum overload current defined in 
M1LoadCurMax (31.10). 
2
T-protection is inactive, if M1OvrLoadTime (31.11) is set to zero. In case the I
2
T-protection is reducing 
A108 MotCurReduce [AlarmWord1 (9.06) bit 7] is set. 
Int. Scaling:  1 == 1 s  Type:  I  Volatile:  N 
31.12 M1RecoveryTime (recovery time I
2
T-function) 
Recovery time during which a reduced current must flow.
 
2
T-protection is inactive, if M1RecoveryTime (31.12) is set to zero. In case the I
2
T-protection is reducing 
A108 MotCurReduce [AlarmWord1 (9.06) bit 7] is set. 
Int. Scaling:  1 == 1 s  Type:  I  Volatile:  N 
Group 34: DCS Control Panel display 
Signal and parameter visualization on the DCS Control Panel: 
 
Setting a display parameter to 0 results in no signal or parameter displayed.
 
Setting a display parameter from 101 to 9999 displays the belonging signal or parameter. If a signal or parameter does not 
exist, the display shows “n.a.”. 
34.01 DispParam1Sel (select signal / parameter to be displayed in the DCS Control Panel row 1) 
Index pointer to the source of the DCS Control Panel first display row [e.g. 101 equals 
MotSpeedFilt (1.01)]. 
Int. Scaling:  1 == 1   Type:  I  Volatile:  N