Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
31.02 M1ModelTime2 (model time 2 constant)
Thermal
time constant for motors with fan/forced cooling if motor fan is switched off.
For motors without fan set
M1ModelTime (31.01) = M1ModelTime2 (31.02).
Int. Scaling: 10 == 1 % Type: I Volatile: N
31.03 M1AlarmLimLoad (alarm limit load)
The drive sets
A107 M1OverLoad [AlarmWord1 (9.06) bit 6] if M1AlarmLimLoad (31.03) - in percent of
- is exceeded. Output value is Mot1TempCalc (1.20).
Int. Scaling: 10 == 1 % Type: I Volatile: N
31.04 M1FaultLimLoad (fault limit load)
The drive trips with
F507 M1OverLoad [FaultWord1 (9.01) bit 6] if M1FaultLimLoad (31.04) - in percent of
- is exceeded. Output value is Mot1TempCalc (1.20).
Int. Scaling: 10 == 1 % Type: I Volatile: N
31.05 M1TempSel (temperature selector)
M1TempSel (31.05)
selects the measured temperature input for the connected motor. The result is displayed
in
Mot1TemopMeas (1.22). Only one single PTC can be connected.
NotUsed motor temperature measurement is blocked, default
1PTC AI2/Con one PTC connected to AI2 on SDCS-CON-F
For more information, see section
Motor protection.
Int. Scaling: 1 == 1 Type: C Volatile: N
31.06 M1AlarmLimTemp (alarm limit temperature)
The drive sets
A106 M1OverTemp [AlarmWord1 (9.06) bit 5] if M1AlarmLimTemp (31.06) is exceeded.
Mot1TempMeas (1.22).
M1TempSel (31.05).
Int. Scaling: 1 == 1 Ω / 1 Type: SI Volatile: N
31.07 M1FaultLimTemp (fault limit temperature)
The drive trips with
F506 M1OverTemp [FaultWord1 (9.01) bit 5] if M1FaultLimTemp (31.07) is exceeded.
Mot1TempMeas (1.22).
M1TempSel (31.05).
Int. Scaling: 1 == 1 Ω / 1 Type: SI Volatile: N