112
AP
Block Parameter Set of block 1
Example:
Add a constant value and an external additional reference to the speed reference:
1. Set 84.04 = 2 (selection of ADD function)
2. Set 84.05 = xx.xx (selection of the speed reference for Input 1)
3. Set 84.06 = xx.xx (selection of an external ref for Input 2)
4. Set 84.07 = 1500 (constant value for Input 3)
5. Set 84.08 = 4000h (because Input 3 = constant Bit 14=1 4000h)
6. Set 86.01 = xx.xx (write processed value to destination parameter for further processing)
7. 84.09: contains the processed value
0
1
84.04
84.05
84.06
84.07
84.08
1.01
1.02
...
99.99
HEX
3
2 1
0 Bit15
0
1
0
1
84.09
86.01
7.01
7.02
...
99.99
I1
I2
I3
ADD
+
O
e.g.
ABS
...
XOR
SB_550_002_block-param_a.ai
Select
Type
Select
Input 1
Select
Input 2
Select
Input 3
Set
Attribute
Act. Signal/
Parameter
table
To use an
input as a
constantvalue,
the bit
belonging to
the inputmust
be set high.
This function offers the opportunity to isolate a
certain bit out of a packed Booleanword. It is used to
connect the Boolean inputs of a functionblock to a
certain bit of a packed Booleanword.With:
Bit 0 == 0000 == 0h
Bit 1 == 0001 == 1h
Bit 15 == 1111 == Fh
input 3
bit sel.
Input
Signal
Output
Write
pointer
Act. Signal/
Parameter
table
Read
pointer of
AP FB
g
roup 84
Dataset table
group 92
INT
Boolean
INT
Boolean
INT
Boolean
Function
input 2
bit sel.
input 1
bit sel.
Blo