Communication
3ADW000379R0501 DCS550 Manual e e
100 = ABB Drives assembly
101 = ABB Drives assembly
Output I/O par 1 (51.08) to Input
I/O par 9 (51.25)
not applicable when using ABB Drives assembly
not applicable when using ABB Drives assembly
If a fieldbus parameter is changed its new value takes
effect only upon setting
FBA PAR REFRESH (51.27) =
RESET or at the next power up of the fieldbus adapter.
* Read-only or automatically detected by DeviceNet adapter
** If HW/SW option (51.04) = 0 (Hardware), the values are automatically set via DIP switches of the RDNA-01
Note:
± 20,000 speed units (decimal) for speed reference [SpeedRef (23.01)] and speed actual [MotSpeed (1.04)]
corresponds to the speed shown in SpeedScaleAct (2.29).
Parameter setting example 2 using User specific assembly
User specific assembly can run with up to 9 data words in each direction. The following table shows the
parameter setting using this profile.
set node address as required
0 = Hardware
1 = Software
not applicable when using User specific assembly
102 = User specific assembly
103 = User specific assembly
Output I/O par 1 (51.08) to Input
I/O par 9
(51.25)
Set these values according table:
Setting of parameter groups 51, 90 and 92 depending on
desired data words and according to the desired numbers
of data words
Defines the length of the User specific assembly in pairs
of data words. E.g. a parameter value of 4 means 4 word
as output and 4 words as input.
If a fieldbus parameter is changed its new value takes
effect only upon setting
FBA PAR REFRESH (51.27) =
RESET or at the next power up of the fieldbus adapter.
* Read-only or automatically detected by DeviceNet adapter
** If HW/SW option (51.04) = 0 (Hardware), the values are automatically set via DIP switches of the RDNA-01
Note:
± 20,000 speed units (decimal) for speed reference [SpeedRef (23.01)] and speed actual [MotSpeed (1.04)]
corresponds to the speed shown in SpeedScaleAct (2.29).