259
Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
Signal / Parameter name
min.
max.
def.
unit
88.31 AnybusModType (last connected serial communication module)
Internally used memory for the last attached serial communication module. This value should only be written
to by:
the DCS550 firmware and
parameter download
Int. Scaling: 1 == 1 Type: I Volatile: N
0
65535
0
-
Group 90: Receiving data sets addresses
Addresses for the received data transmitted from the overriding control to the drive.
The format is
xxyy, with: xx = group and yy = index.
90.01 DsetXVal1 (data set X value 1)
Data set 1
value 1 (interval: 3 ms).
Default setting of 701 equals
MainCtrlWord (7.01).
Int. Scaling: 1 == 1 Type: I Volatile: N
0
9999
701
-
90.02 DsetXVal2 (data set X value 2)
Data set 1 value 2 (interval: 3 ms).
Default setting of 2301 equals
SpeedRef (23.01).
Int. Scaling: 1 == 1 Type: I Volatile: N
0
9999
2301
-
90.03 DsetXVal3 (data set X value 3)
Data set 1 value 3 (interval: 3 ms).
Default setting of 2501 equals
TorqRefA (25.01).
Int. Scaling: 1 == 1 Type: I Volatile: N
0
9999
2501
-
90.04 DsetXplus2Val1 (data set X+2 value 1)
Data set 3 value 1 (interval: 3 ms).
Default setting of 702 equals
AuxCtrlWord (7.02).
Int. Scaling: 1 == 1 Type: I Volatile: N
0
9999
702
-
90.05 DsetXplus2Val2 (data set X+2 value 2)
Data set 3 value 2 (interval: 3 ms).
Default setting of 703 equals
AuxCtrlWord2 (7.03).
Int. Scaling: 1 == 1 Type: I Volatile: N
0
9999
703
-
90.06 DsetXplus2Val3 (data set X+2 value 3)
Data set 3 value 3 (interval: 3 ms).
Int. Scaling: 1 == 1 Type: I Volatile: N
0
9999
0
-
90.07 DsetXplus4Val1 (data set X+4 value 1)
Data set 5 value 1 (interval: 3 ms).
Int. Scaling: 1 == 1 Type: I Volatile: N
0
9999
0
-
90.08 DsetXplus4Val2 (data set X+4 value 2)
Data set 5 value 2 (interval: 3 ms).
Int. Scaling: 1 == 1 Type: I Volatile: N
0
9999
0
-
90.09 DsetXplus4Val3 (data set X+4 value 3)
Data
set 5 value 3 (interval: 3 ms).
Data set address =
Ch0 DsetBaseAddr (70.24) + 4.
Int. Scaling: 1 == 1 Type: I Volatile: N
0
9999
0
-
e.g. DWLGroup
Data words
Overriding control
90
Address
assignment
SDCS-CON-F
Serial communication via
slot 1 of SDCS-CON-F
1
...
10