Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
Signal / Parameter name
min.
max.
def.
unit
Group 16: System control inputs
16.01 Unused
16.02 ParLock (parameter lock)
The user can lock all parameters by means of
ParLock (16.02) and SysPassCode (16.03)
. To lock parameters
set
SysPassCode (16.03) to the desired value and change ParLock (16.02) from Open to Locked. Unlocking
of parameters is only possible if the proper pass code (the value
that was present during locking) is used. To
open parameters set
SysPassCode (16.03) to the proper value and change ParLock (16.02) from Locked to
Open
.
After the parameters are
locked or opened the value in SysPassCode (16.03) is automatically changed to 0:
0 =
Open parameter change possible, default
1 =
Locked parameter change not possible
Int. Scaling: 1 == 1 Type: C Volatile: N
Open
Locked
Open
-
16.03 SysPassCode (system pass code)
The
SysPassCode (16.03) is a number between 1 and 30,000 to lock all parameters by means of ParLock
(16.02)
. After using Open or Locked SysPassCode (16.03) is automatically set back to zero.
Attention:
Do not forget the pass co
de!
Int. Scaling: 1 == 1 Type: I Volatile: Y
0
30000
0
-
16.04 LocLock (local lock)
Local control can be disabled by setting
LocLock (16.04) to True. If LocLock (16.04) is released in local
control, it becomes valid after the next changeover to remote control. No pass code is required to change
LocLock (16.04):
0 =
False local control released, default
1 =
True local control blocked
Int. Scaling: 1 == 1 Type: C Volatile: N
False
True
False
-
16.05 Unused
16.06 ParApplSave (save parameters)
If parameters are written to cyclic, e.g. from an overriding control, they are only stored in the RAM and not in
the flash. By means of
ParApplSave (16.06), all parameter values are saved from the RAM into the flash:
0 =
Done parameters are saved, default
1 =
Save saves the actual used parameters into the flash
After
the action is finished ParApplSave (16.06) is changed back to Done. This will take max. 1 second.
Note:
Do not use the parameter save function unnecessarily
Note:
Parameters changed by DCS Control Panel or commissioning tools are immediately saved into the flash.
Int. Scaling: 1 == 1 Type: C Volatile: Y
Done
Save
Done
-
16.07 - 16.10 Unused
16.11 SetSystemTime (set the drive’s system time)
Sets the time of the converter in minutes. The system time can be either set by means of
SetSystemTime
(16.11)
or via the DCS Control Panel.
Int. Scaling: 1 == 1 min Type: I Volatile: Y
0
64000
0
min
16.12 - 16.13 Unused
16.14 ToolLinkConfig (tool link configuration)
The communication speed of the serial communication for the commissioning tool and the application program
tool can be selected with
ToolLinkConfig (16.14):
0 =
9600 9600 Baud
1 =
19200 19200 Baud
2 =
38400 38400 Baud, default
3 =
57600 57600 Baud
4 =
115200 115200 Baud
If
ToolLinkConfig (16.14) is changed its new value is taken over after the next power up.
Int. Scaling: 1 == 1 Type: C Volatile: N
9600
115200
38400