261
Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
92.10 DsetXplus7Val1 (data set X+7 value 1)
Data set 8 value 1 (interval: 3 ms).
Default setting of 904 equals
FaultWord4 (9.04).
Int. Scaling: 1 == 1 Type: I Volatile: N
97.01 TypeCode (type code)
TypeCode (97.01)
is preset in the factory and is write protected. It identifies the drives current-, voltage-,
temperature measurement and its quadrant type. To un
-protect the type code set ServiceMode (99.06) =
. The change of the type code is immediately taken over and ServiceMode (99.06) is
automatically set back to
NormalMode:
None no type code set
S01-0020-05 type code, see table
S02-1000-05 type code, see table
The drive’s basic type code: DCS550-AAX-YYYY-ZZ
Standard converter modules
2 anti parallel bridges (4-Q)
230 V
- 525 V
Int. Scaling: 1 == 1 Type: C Volatile: Y
97.04 S MaxBrdgTemp (set: maximum bridge temperature)
Adjustment of the converters heat sink temperature tripping level in degree centigrade:
= take value from TypeCode (97.01), default
= take value from S MaxBrdgTemp (97.04)
= the temperature supervision is inactive, if S MaxBrdgTemp (97.04) is set to 150 °C
This value overrides the type code and is immediately visible in
MaxBridgeTemp (4.17).
Int. Scaling: 1 == 1 °C Type: I Volatile: N
97.07 S BlockBridge2 (set: block bridge 2)
Bridge 2 can be blocked:
Auto operation mode is taken from TypeCode (97.01), default
BlockBridge2 block bridge 2 (== 2-Q operation), for e.g. 2-Q rebuild kits
RelBridge2 release bridge 2 (== 4-Q operation), for e.g. 4-Q rebuild kits
This value overrides the type code and is immediately visible in
QuadrantType (4.15).
Int. Scaling: 1 == 1 Type: C Volatile: N
97.09 MainsCompTime (mains compensation time)
Mains voltage compensation filter time constant
. Is used for the mains voltage compensation at the current
output.
Setting MainsCompTime (97.09) to 1000 ms disables the mains voltage compensation.
Int. Scaling: 1 == 1 ms Type: I Volatile: N