261
Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
Signal / Parameter name
min.
max.
def.
unit
92.10 DsetXplus7Val1 (data set X+7 value 1)
Data set 8 value 1 (interval: 3 ms).
Default setting of 904 equals
FaultWord4 (9.04).
Int. Scaling: 1 == 1 Type: I Volatile: N
0
9999
904
-
Group 97: Measurements
97.01 TypeCode (type code)
TypeCode (97.01)
is preset in the factory and is write protected. It identifies the drives current-, voltage-,
temperature measurement and its quadrant type. To un
-protect the type code set ServiceMode (99.06) =
SetTypeCode
. The change of the type code is immediately taken over and ServiceMode (99.06) is
automatically set back to
NormalMode:
0 =
None no type code set
1 =
S01-0020-05 type code, see table
to
xxx =
S02-1000-05 type code, see table
The drive’s basic type code: DCS550-AAX-YYYY-ZZ
Product family:
DCS550
Type:
AA
= S0
Standard converter modules
Bridge type:
X
= 1
Single bridge (2-Q)
= 2
2 anti parallel bridges (4-Q)
Module type:
YYYY
=
Rated DC current
Rated AC voltage:
ZZ
= 05
230 V
AC
- 525 V
AC
Int. Scaling: 1 == 1 Type: C Volatile: Y
None
S01-5203-05
factory preset value
-
97.02 - 97.03 Unused
97.04 S MaxBrdgTemp (set: maximum bridge temperature)
Adjustment of the converters heat sink temperature tripping level in degree centigrade:
0 °C
= take value from TypeCode (97.01), default
1 °C to 149 °C
= take value from S MaxBrdgTemp (97.04)
150 °C
= the temperature supervision is inactive, if S MaxBrdgTemp (97.04) is set to 150 °C
This value overrides the type code and is immediately visible in
MaxBridgeTemp (4.17).
Int. Scaling: 1 == 1 °C Type: I Volatile: N
0
150
0
°C
97.05 - 97.06 Unused
97.07 S BlockBridge2 (set: block bridge 2)
Bridge 2 can be blocked:
0 =
Auto operation mode is taken from TypeCode (97.01), default
1 =
BlockBridge2 block bridge 2 (== 2-Q operation), for e.g. 2-Q rebuild kits
2 =
RelBridge2 release bridge 2 (== 4-Q operation), for e.g. 4-Q rebuild kits
This value overrides the type code and is immediately visible in
QuadrantType (4.15).
Int. Scaling: 1 == 1 Type: C Volatile: N
Auto
RelBridge2
Auto
-
97.08 Unused
97.09 MainsCompTime (mains compensation time)
Mains voltage compensation filter time constant
. Is used for the mains voltage compensation at the current
controller
output.
Setting MainsCompTime (97.09) to 1000 ms disables the mains voltage compensation.
Int. Scaling: 1 == 1 ms Type: I Volatile: N
0
1000
10
ms
97.10 - 97.12 Unused