221
Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
30.32 ExtAlarmSel (external alarm selector)
The drive sets
A126 ExternalDI [AlarmWord2 (9.07) bit 9] if a binary input for an external alarm is selected
NotUsed default
DI1 1 = fault, 0 = no fault
DI2 1 = fault, 0 = no fault
DI3 1 = fault, 0 = no fault
DI4 1 = fault, 0 = no fault
DI5 1 = fault, 0 = no fault
DI6 1 = fault, 0 = no fault
DI7 1 = fault, 0 = no fault
DI8 1 = fault, 0 = no fault
DI9 1 = fault, 0 = no fault. Only available with digital extension board
DI10 1 = fault, 0 = no fault. Only available with digital extension board
DI11 1 = fault, 0 = no fault. Only available with digital extension board
MCW Bit11 1 = fault, 0 = no fault, MainCtrlWord (7.01) bit 11
MCW Bit12 1 = fault, 0 = no fault, MainCtrlWord (7.01) bit 12
MCW Bit13 1 = fault, 0 = no fault, MainCtrlWord (7.01) bit 13
MCW Bit14 1 = fault, 0 = no fault, MainCtrlWord (7.01) bit 14
MCW Bit15 1 = fault, 0 = no fault, MainCtrlWord (7.01) bit 15
Int. Scaling: 1 == 1 Type: C Volatile: N
30.35 FB TimeOut (fieldbus time out)
Time delay before a communication break with a fieldbus is declared. Depending on the setting of
ComLossCtrl (30.28)
either F528 FieldBusCom [FaultWord2 (9.02) bit 11] or A128 FieldBusCom
AlarmWord2 (9.07) bit 11] is set.
The communication fault and alarm are inactive, if
FB TimeOut (30.35) is set to 0 ms.
Int. Scaling: 1 == 1 ms Type: I Volatile: N
30.36 SpeedFbFltMode (speed feedback fault mode)
SpeedFbFltMode (30.36)
determines the reaction of all faults of trip level 3:
CoastStop The firing pulses are immediately set to 150 degrees to decrease the armature current.
When the armature current is zero the firing pulses are blocked, the contactors are
opened, field exciter and fans are stopped.
DynBraking dynamic braking
does not apply to communication faults.
Int. Scaling: 1 == 1 Type: C Volatile: N
Group 31: Motor temperature
31.01 M1ModelTime (model time constant)
Thermal time constant for motors with fan/forced cooling. The time within the temperature rises to 63% of
its
The motor thermal model is blocked, if
M1ModelTime (31.01) is set to zero.
Mot1TempCalc (1.20) is saved at power down of the drives electronics. Energizing the drives
electronics the very first time the motor's ambient temp
erature is set to 30°C.
WARNING! The model does not protect the motor if it is not properly cooled e.g. due to dust and dirt.
Int. Scaling: 10 == 1 s Type: I Volatile: N