207
Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
21.18 FldHeatSel (field heat selector)
FldHeatSel (21.18)
releases the field heating:
NotUsed field heating is off, default
On field heating is on, as long as: On = 0 [UsedMCW (7.04) bit 0], Off2N = 1
[UsedMCW (7.04) bit 1] and Off3N = 1 [UsedMCW
(7.04) bit 2]
OnRun field heating is on as long as: On = 1, Run = 0 [UsedMCW (7.04) bit 3], Off2N = 1
and Off3N = 1
The field heating reference is set with M1FldHeatRef (44.04). Field heating can be disabled when the
reference is set to zero.
Field nominal current is set with M1NomFldCur (99.11).
In case field heating is used following settings apply:
MainContCtrlMode (21.16) = On
FldHeatSel (21.18) = OnRun
Int. Scaling: 1 == 1 Type: C Volatile: N
22.01 AccTime1 (acceleration time 1)
The time within the drive will accelerate from zero speed to
SpeedScaleAct (2.29). AccTime1 (22.01) can be
Ramp2Sel (22.11).
Int. Scaling: 100 == 1 s Type: I Volatile: N
22.02 DecTime1 (deceleration time 1)
The time within the drive will decelerate from
SpeedScaleAct (2.29) to zero speed. DecTime1 (22.02) can be
Ramp2Sel (22.11).
Int. Scaling: 100 == 1 s Type: I Volatile: N
22.04 E StopRamp (emergency stop ramp)
The time within the drive will decelerate from
SpeedScaleAct (2.29) to zero speed. When emergency stop is
E StopMode (21.04) = RampStop or as reaction to a fault of trip level 4 and FaultStopMode
= RampStop.
Int. Scaling: 10 == 1 s Type: I Volatile: N
22.05 ShapeTime (shape time)
Speed
reference softening time. This function is bypassed during an emergency stop:
Int. Scaling: 100 == 1 s Type: I Volatile: N