276 
   
 
Fault tracing
 
3ADW000379R0501 DCS550 Manual e e 
Fault tracing 
Chapter overview 
This chapter describes the protections and fault tracing of the drive. 
Fault modes 
Depending on the trip level of the fault, the drive reacts differently. The drive’s reaction to a fault with trip level 
1 and 2 is fixed. See also paragraph Fault signals
 of this manual. The reaction to a fault of level 3 and 4 can 
be chosen by means of SpeedFbFltMode (30.36) respectively FaultStopMode (30.30). 
Converter protection 
Auxiliary undervoltage 
If the auxiliary supply voltage fails while the drive is in RdyRun state (MSW bit 1), fault F501 AuxUnderVolt is 
generated. 
Armature overcurrent 
The nominal value of the armature current is set with M1NomCur (99.02). The overcurrent level is set by 
means of ArmOvrCurLev (30.09). Additionally the actual current is monitored against the overcurrent level of 
the converter module. The converter’s actual overcurrent level can be read from ConvOvrCur (4.16). 
Exceeding one of the two levels causes F502 ArmOverCur. 
Converter overtemperature 
The maximum temperature of the bridge can be read from MaxBridgeTemp (4.17) and is automatically set by 
TypeCode (97.01) or manually set by S MaxBrdgTemp (97.04). 
Exceeding this level causes F504 ConvOverTemp. The threshold for A104 ConvOverTemp is 5 °C below 
the tripping level. The measured temperature can be read from BridgeTemp (1.24). 
If the measured temperature drops below minus 10 °C, F504 ConvOverTemp is generated. 
Auto-reclosing (mains undervoltage) 
Auto-reclosing allows continuing drive operation immediately after a short mains undervoltage without any 
additional functions in the overriding control system. 
In order to keep the overriding control system and the drive control electronics running through short mains 
undervoltage, an UPS is needed for the 115/230 V
AC
 auxiliary voltages. Without the UPS all DI like e.g. E-
stop, start inhibition, acknowledge signals etc. would have false states and trip the drive although the system 
itself could stay alive. In addition, the control circuits of the main contactor must be supplied during the mains 
undervoltage. 
Auto-reclosing defines whether the drive trips immediately with F512 MainsLowVolt or if the drive will 
continue running after the mains voltage returns. To activate the auto-reclosing set PwrLossTrip (30.21) = 
Delayed. 
 
Short mains undervoltage 
The supervision of mains undervoltage has two levels: 
1.  UNetMin1 (30.22) alarm, protection and trip level 
2.  UNetMin2 (30.23) trip level 
If the mains voltage falls below UNetMin1 (30.22) but stays above UNetMin2 (30.23), the following actions 
take place: 
1.  the firing angle is set to ArmAlphaMax (20.14), 
2.  single firing pulses are applied in order to extinguish the current as fast as possible, 
3.  the controllers are frozen, 
4.  the speed ramp output is updated from the measured speed and