Mechanical installation
3ADW000379R0501 DCS550 Manual e e
Cabinet installation
The required distance between parallel units is five millimeters (0.2 in.) in installations without front cover. The
cooling air entering the unit must not exceed +40°C (+104°F).
Preventing cooling air recirculation
Unit above another
Prevent air recirculation inside and outside the cabinet
Lead the exhaust cooling air away from the unit
above. Distances see chapter Dimensions.
BG_800_004_luft_a.ai
Hot area
Cool area
Main air flow in
Air baffle plates
Main air flow out
max.+40°C
BG_800_003_luft_a.ai
Air baffle plate
Airflow