Electrical installation
3ADW000379R0501 DCS550 Manual e e
Pulse encoder connection principles
Two different incremental encoder connections are available:
1. differential connection; pulse encoders generating
either voltage or current signals can be used,
2.
single-ended (push pull) connection; only voltage
signals can be used
In case of a single ended 5 V encoder the jumper S4 has be set to a neutral position. To get a threshold lower
than 5 V each terminal X3:2, 4, 6 must be connected via a resistor R to GND.
Cable length
The maximum distance between pulse encoder and interface board dependents on the voltage drop of the
connecting lines and on the output and input configuration of the used components. Use cables according to
the table below. The voltage regulator can compensate the voltage drop caused by the cable. Use twisted pair
cables with pair shielding plus overall shielding:
Cable length
Parallel wires for power source & GND
Cable used
0 to 50 m
1 * 0.25 mm²
12 * 0.25 m
50 to 100 m
2 * 0.25 mm²
12 * 0.25 m
100 to 150 m
3 * 0.25 mm²
14 * 0.25 m
Cable length
Parallel wires for power source & GND
Cable used
0 to 164 ft.
1 * 24 AWG
12 * 24 AWG
164 to 328 ft.
2 * 24 AWG
12 * 24 AWG
328 to 492 ft.
3 * 24 AWG
14 * 24 AWG