252
Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
83.01 AdapProgCmd (AP command)
Selects the operation mode for AP:
Stop stop, AP is not running and cannot be edited, default
Start running, AP is running and cannot be edited
Edit edit, AP is not running and can be edited
SingleCycle AP runs only once. If a breakpoint is set with BreakPoint (83.06), AP will stop before the
breakpoint. After the SingleCycle AdapProgCmd (83.01) is automatically set back to
Stop.
SingleStep Runs only one function block. LocationCounter (84.03)
shows the function block number,
which will be executed during the next SingleStep. After a SingleStep AdapProgCmd
(83.01) is automatically set back to Stop. LocationCounter (84.03) shows the next
function block to be executed. To reset LocationCounter (84.03)
to the first function block
set AdapProgCmd (83.01) to Stop again (even if it is already set to Stop).
[AlarmWord3 (9.08) bit 3] is set when TimeLevSel (83.04) is not set to 5 ms, 20 ms,
or 500 ms but AdapProgCmd (83.01) is set to Start, SingleCycle or SingleStep
= Start, SingleCycle or SingleStep is only valid, if AdapPrgStat (84.01) ≠ Running.
Int. Scaling: 1 == 1 Type: C Volatile: N
83.02 EditCmd (edit command)
Edit AP.
EditCmd (83.02) is automatically set back to Done after the chosen action is finished:
Done no action or edit of AP completed, default
Push Shifts the function block in the spot defined by EditBlock (83.03) and all subsequent
function blocks one spot forward. A new function block can be placed in the now empty
spot by programming its parameter set as usual.
Example:
A new function block needs to be placed in between the function block number four
(84.22) to (84.27) and five (84.28) to (84.33). In order to do this:
1. set AdapProgCmd (83.01) = Edit
2. set EditBlock (83.03) = 5 (selects function block 5 as the desired spot for the new
function block)
3. set EditCmd (83.02) = Push (shifts function block 5 and all subsequent function
blocks one spot forward)
4. program empty spot 5 by means of (84.28) to (84.33)
Delete Deletes the function block in the spot defined by EditBlock (83.03) and shifts all
subsequent function blocks one spot backward. To delete all function blocks set
EditBlock (83.03) = 17.
Protect Turns all parameters of AP into protected mode (parameters cannot be read or written
to). Before using the Protect command set the pass code by means of PassCode
(83.05).
Attention: Do not forget the pass code!
Unprotect Reset of protected mode. Before the Unprotect command can be used, PassCode
(83.05) has to be set.
Attention: Use the proper pass code!
Int. Scaling: 1 == 1 Type: C Volatile: Y
83.03 EditBlock (edit block)
Defines the function block which is selected by
EditCmd (83.02) = Push or Delete. After a Push or Delete
is automatically set back to 1.
To delete all function blocks set
EditBlock (83.03) = 17.
Int. Scaling: 1 == 1 Type: I Volatile: Y