Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
Signal / Parameter name
min.
max.
def.
unit
Group 66: Winder program control
66.01 WiProgCmd (winder program, command)
Selects the operation mode for
the winder program:
0 =
Stop Execution of winder blocks stopped. Speed control chain parameters are set back to
default parameter values, e.g. SpeedCorr (23.04), SpeedRefScale (23.16), LoadComp
(26.02).
1 =
Start Enable execution of winder blocks if a winder macro is selected.
2 =
Edit reserved
3 =
EditExecTab reserved
4 =
SingleCycle reserved
5 =
SingleStep reserved
Int. Scaling: 1 == 1 Type: C Volatile: N
Stop
SingleStep
Stop
-
66.02 - 66. 03 Unused
66.04 WiUserMode (winder program, user mode)
0 =
Standard reserved
1 =
Expert reserved
Int. Scaling: 1 == 1 Type: C Volatile: N
Standard
Expert
Standard
66.05 WiPassCode
reserved
Int. Scaling: 1 == 1 Type: C Volatile: N
0
30000
0
-