197 
   
 
Signal and parameter list 
3ADW000379R0501 DCS550 Manual e e 
14.16 DO8BitNo (digital output 8 bit number) 
Bit number of the signal/parameter selected with 
DO8Index (14.15). 
Int. Scaling:  1 == 1   Type:  I  Volatile:  N 
15.01 IndexAO1 (analog output 1 index) 
Analog output 1 is controlled by a source (signal/parameter) selected with 
IndexAO1 (15.01). The format is -
, with: - = negate analog output, xx = group and yy = index. 
Int. Scaling:  1 == 1 Type:  SI  Volatile:  N 
15.02 CtrlWordAO1 (control word analog output 1) 
Analog output 1 can be written to via 
CtrlWordAO1 (15.02) using AP or overriding control if IndexAO1 (15.01) 
is set to zero. Further description see 
group 19 Data Storage. 
Int. Scaling:  1 == 1 Type:  SI  Volatile:  Y 
32768
15.03 ConvModeAO1 (convert mode analog output 1) 
Analog output 1 signal offset:
 
10V Bi    -10 V to 10 V bipolar output, default 
0V-10V Uni  0 V to 10 V unipolar output 
2V-10V Uni  2 V to 10 V unipolar output 
5V Offset  
5 V offset in the range 0 V to 10 V for testing or indication of bipolar signals (e.g. torque, 
speed, etc.) 
6V Offset  
6 V offset in the range 2 V to 10 V for testing or indication of bipolar signals (e.g. torque, 
speed, etc.) 
0V-10V Abs  absolute 0 V to 10 V unipolar output (negative values are shown positive) 
Int. Scaling:  1 == 1   Type:  C   Volatile:  N 
10V Bi 
10V Bi 
15.04 FilterAO1 (filter analog output 1) 
Analog output 1 filter time.
 
Int. Scaling:  1 == 1 ms  Type:  I  Volatile:  N 
15.05 ScaleAO1 (scaling analog output 1) 
100 % of the signal/parameter selected with 
IndexAO1 (15.01) is scaled to the voltage in ScaleAO1 (15.05). 
 
In case the min. / max. voltage (
±10 V) of analog output 1 should equal ±250 % of TorqRefUsed (2.13), set: 
  IndexAO1 (15.01) = 213, 
  ConvModeAO1 (15.03) = 
10V Bi and 
  ScaleAO1 (15.05) = 4000 mV 
Int. Scaling:  1 == 1 mV  Type:  I  Volatile:  N 
15.06 IndexAO2 (analog output 2 index) 
Analog output 2 is controlled by a source (signal/parameter) selected with 
IndexAO2 (15.06). The format is -
, with: - = negate analog output, xx = group and yy = index. 
Int. Scaling:  1 == 1   Type:  SI  Volatile:  N 
15.07 CtrlWordAO2 (control word analog output 2) 
Analog output 2 can be written to via 
CtrlWordAO2 (15.07) using AP or overriding control if IndexAO2 (15.06) 
is set to zero. Further description see 
group 19 Data Storage. 
Int. Scaling:  1 == 1 Type:  SI  Volatile:  Y 
32768
15.08 ConvModeAO2 (convert mode analog output 2) 
Analog output 2 signal offset:
 
10V Bi    -10 V to 10 V bipolar output, default 
0V-10V Uni  0 V to 10 V unipolar output 
2V-10V Uni  2 V to 10 V unipolar output 
5V Offset  
5 V offset in the range 0 V to 10 V for testing or indication of bipolar signals (e.g. torque, 
speed, etc.) 
6V Offset   6 V offset in the range 2 V to 10 V for testing or indication of bipolar signals (e.g. torque, 
speed, etc.) 
0V-10V Abs  absolute 0 V to 10 V unipolar output (negative values are shown positive) 
Int. Scaling:  1 == 1   Type:  C  Volatile:  N 
10V Bi 
10V Bi