14.16 DO8BitNo (digital output 8 bit number)
Bit number of the signal/parameter selected with
DO8Index (14.15).
Int. Scaling: 1 == 1 Type: I Volatile: N
15.01 IndexAO1 (analog output 1 index)
Analog output 1 is controlled by a source (signal/parameter) selected with
IndexAO1 (15.01). The format is -
, with: - = negate analog output, xx = group and yy = index.
Int. Scaling: 1 == 1 Type: SI Volatile: N
15.02 CtrlWordAO1 (control word analog output 1)
Analog output 1 can be written to via
CtrlWordAO1 (15.02) using AP or overriding control if IndexAO1 (15.01)
is set to zero. Further description see
group 19 Data Storage.
Int. Scaling: 1 == 1 Type: SI Volatile: Y
32768
15.03 ConvModeAO1 (convert mode analog output 1)
Analog output 1 signal offset:
10V Bi -10 V to 10 V bipolar output, default
0V-10V Uni 0 V to 10 V unipolar output
2V-10V Uni 2 V to 10 V unipolar output
5V Offset
5 V offset in the range 0 V to 10 V for testing or indication of bipolar signals (e.g. torque,
speed, etc.)
6V Offset
6 V offset in the range 2 V to 10 V for testing or indication of bipolar signals (e.g. torque,
speed, etc.)
0V-10V Abs absolute 0 V to 10 V unipolar output (negative values are shown positive)
Int. Scaling: 1 == 1 Type: C Volatile: N
10V Bi
10V Bi
15.04 FilterAO1 (filter analog output 1)
Analog output 1 filter time.
Int. Scaling: 1 == 1 ms Type: I Volatile: N
15.05 ScaleAO1 (scaling analog output 1)
100 % of the signal/parameter selected with
IndexAO1 (15.01) is scaled to the voltage in ScaleAO1 (15.05).
In case the min. / max. voltage (
±10 V) of analog output 1 should equal ±250 % of TorqRefUsed (2.13), set:
IndexAO1 (15.01) = 213,
ConvModeAO1 (15.03) =
10V Bi and
ScaleAO1 (15.05) = 4000 mV
Int. Scaling: 1 == 1 mV Type: I Volatile: N
15.06 IndexAO2 (analog output 2 index)
Analog output 2 is controlled by a source (signal/parameter) selected with
IndexAO2 (15.06). The format is -
, with: - = negate analog output, xx = group and yy = index.
Int. Scaling: 1 == 1 Type: SI Volatile: N
15.07 CtrlWordAO2 (control word analog output 2)
Analog output 2 can be written to via
CtrlWordAO2 (15.07) using AP or overriding control if IndexAO2 (15.06)
is set to zero. Further description see
group 19 Data Storage.
Int. Scaling: 1 == 1 Type: SI Volatile: Y
32768
15.08 ConvModeAO2 (convert mode analog output 2)
Analog output 2 signal offset:
10V Bi -10 V to 10 V bipolar output, default
0V-10V Uni 0 V to 10 V unipolar output
2V-10V Uni 2 V to 10 V unipolar output
5V Offset
5 V offset in the range 0 V to 10 V for testing or indication of bipolar signals (e.g. torque,
speed, etc.)
6V Offset 6 V offset in the range 2 V to 10 V for testing or indication of bipolar signals (e.g. torque,
speed, etc.)
0V-10V Abs absolute 0 V to 10 V unipolar output (negative values are shown positive)
Int. Scaling: 1 == 1 Type: C Volatile: N
10V Bi
10V Bi