Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
Signal / Parameter name
min.
max.
def.
unit
Group 99: Start-up data
99.01 Language (language)
Select language:
0 =
English default
1 = reserved
2 =
Deutsch
3 =
Italiano
4 =
Español
5 = reserved
6 = reserved
7 =
Français
Int. Scaling: 1 == 1 Type: C Volatile: N
English
English
English
-
99.02 M1NomVolt (nominal DC voltage)
Nominal armature voltage (DC) from the motor rating plate.
Int. Scaling: 1 == 1 V Type: I Volatile: N
5
700
350
V
99.03 M1NomCur (nominal DC current)
Nominal armature current (DC) from the motor rating plate.
Int. Scaling: 1 == 1 A Type: I Volatile: N
0
1000
0
A
99.04 M1BaseSpeed (base speed)
Base speed from the rating plate, usually the field weak point.
M1BaseSpeed (99.04) is must be set in the
range of:
0.2 to 1.6 times of SpeedScaleAct (2.29).
If the scaling is out of range
A124 SpeedScale [AlarmWord2 (9.07) bit 7] is generated.
Int. Scaling: 10 == 1 rpm Type: I Volatile: N
10
6500
1500
rpm
99.05 Unused
99.06 ServiceMode (service mode)
ServiceMode (99.06)
contains several test- and auto tuning procedures.
The drive mode is automatically set to
NormalMode after an autotuning procedure or after the thyristor
diagnosis is finished or failed. In case errors occur during the selected procedure
A121 AutotuneFail
[
AlarmWord2 (9.07) bit 4] is generated. The reason of the error can be seen in Diagnosis (9.11).
Set
TypeCode is automatically set to NormalMode after the next power up.
0 =
NormalMode normal operating mode depending on OperModeSel (43.01), default
1 =
ArmCurAuto autotuning armature current controller
2 =
FieldCurAuto autotuning field current controller
3 =
EMF FluxAuto autotuning EMF controller and flux linearization
4 =
SpdCtrlAuto autotuning speed controller
5 =
SpdFbAssist test speed feedback, see M1SpeedFbSel (50.03), M1EncPulseNo (50.04) and
M1TachoVolt1000 (50.13)
6 =
TachFineTune tacho fine tuning, see M1TachoAdjust (50.12)
7 =
ThyDiagnosis thyristor diagnosis, the result is shown in Diagnosis (9.11)
8 =
FindDiscCur find discontinuous current limit
9 =
SetTypeCode set type code, releases following parameters:
TypeCode (97.01)
10 =
LD FB Config reserved for future use (load fieldbus configuration file)
Note:
The reference chain is blocked while ServiceMode (99.06)
NormalMode.
Int. Scaling: 1 == 1 Type: C Volatile: Y
NormalMode
FindDiscCur
NormalMode
-