Signal and parameter list
Signal / Parameter name
min.
max.
def.
unit
98.06 AIO ExtModule (analog extension module)
RAIO
-xx extension module interface selection. AIO ExtModule (98.06) releases AI5, AI6, AO3 and AO4.
The module can be connected in option slot 1 or 3:
0 =
NotUsed no RAIO-xx is used, default
1 =
Slot1 RAIO-xx is connected in option slot 1
2 = reserved
3 =
Slot3 RAIO-xx is connected in option slot 3
The drive trips with
F508 I/OBoardLoss [FaultWord1 (9.01) bit 7], if the RAIO-
xx extension module is chosen,
but not connected or faulty.
Attention:
To ensure proper connection and c
ommunication of the RAIO-xx board with the SDCS-CON-
F use the screws
included in the scope of delivery.
Switches on the 1
st
RAIO-xx:
Configuration switch (S2)
Select the operation of the analog inputs using the configuration DIP switch (S2) on the
circuit board of the
module. The drive parameters must be set accordingly.
Input mode selection:
In bipolar mode, the analog inputs can handle positive and negative signals. The resolution of the A/D
conversion is 11 data bits (+ 1 sign bit). In unipolar m
ode (default), the analog inputs can handle positive
signals only. The resolution of the A/D conversion is 12 data bits.
Input signal type selection:
Each input can be used with a current or voltage signal.
Int. Scaling: 1 == 1 Type: C Volatile: N