98.04 DIO ExtModule2 (digital extension module 2)
Second RDIO
-xx extension module interface selection. DIO ExtModule2 (98.04) releases DI12, DI13, DI14,
The module can be connected in option slot 1 or 3:
NotUsed no second RDIO-xx is used, default
Slot1 second RDIO-xx is connected in option slot 1
Slot3 second RDIO-xx is connected in option slot 3
F508 I/OBoardLoss [FaultWord1 (9.01) bit 7], if the RDIO-
xx extension module is chosen,
but not connected or faulty.
For faster input signal detection disable the hardware filters of the RDIO-xx by means of dip switch S2.
Always have the hardware filter enabled when an AC signal is connected.
The digital inputs are available via DI StatWord (8.05)
The digital outputs are available via DO CtrlWord (7.05).
per connection and communication of the RDIO-xx board with the SDCS-CON-
F use the screws
included in the scope of delivery.
nd
RDIO-xx:
Configuration switch (S2)
For faster detection the hardware filter of the digital input in question
can be disabled. Disabling the hardware
filtering will however reduce the noise immunity of the input.
Int. Scaling: 1 == 1 Type: C Volatile: N