Signal and parameter list
Signal / Parameter name
min.
max.
def.
unit
98.03 DIO ExtModule1 (digital extension module 1)
First RDIO
-xx extension module interface selection. DIO ExtModule1 (98.03) releases DI9, DI10, DI11, DO9
and DO10.
The module can be connected in option slot 1 or 3:
0 =
NotUsed no first RDIO-xx is used, default
1 =
Slot1 first RDIO-xx is connected in option slot 1
2 = reserved
3 =
Slot3 first RDIO-xx is connected in option slot 3
The drive trips with
F508 I/OBoardLoss [FaultWord1 (9.01) bit 7], if the RDIO-
xx extension module is chosen,
but not connected or faulty.
Notes:
For faster input signal detection disable the hardware filters of the RDIO-xx by means of dip switch S2.
Always have the hardware filter enabled when an AC signal is connected.
The digital outputs are available via DO CtrlWord (7.05).
Attention:
To ensure proper connection and communica
tion of the RDIO-xx board with the SDCS-CON-
F use the screws
included in the scope of delivery.
Switches on the 1
st
RDIO-xx:
Configuration switch (S2)
For faster detection the hardware filter of the digital input in question can be disabled. Disabling
the hardware
filtering will however reduce the noise immunity of the input.
Int. Scaling: 1 == 1 Type: C Volatile: N
NotUsed
Slot3
NotUsed
-