268
Signal and parameter list
Signal / Parameter name
min.
max.
def.
unit
99.07 ApplRestore (application restore)
Setting
ApplRestore (99.07) = Yes
starts the loading / storing of the macro (preset parameter set) selected by
means of
ApplMacro (99.08). ApplRestore (99.07) is automatically set back to Done after the chosen action
is
finished:
0 =
Done no action or macro change completed, default
1 =
Yes macro selected with ApplMacro (99.08) will be loaded into the drive
Notes:
Macro changes are only accepted in Off state [MainStatWord (8.01) bit 1 = 0].
It takes about 2 s, until the new parameter values are active.
Int. Scaling: 1 == 1 Type: C Volatile: Y
Done
Yes
Done
-
99.08 ApplMacro (application macro)
ApplMacro (99.08)
selects the macro (preset parameter sets) to be loaded / stored into the RAM and flash. In
addition to the preset macros, two user
-defined macros (User1 and User2) are available.
The operation selected by
ApplMacro (99.08) is started immediately by setting ApplRestore (99.07) = Yes.
ApplMacro (99.08)
is automatically set back to NotUsed after the chosen action is finished. The selected
macro is shown in
MacroSel (8.10):
0 =
NotUsed default
1 =
Factory load macro factory (default parameter set) into RAM and flash - User1 and User2
will not be influenced
2 =
User1Load load macro User1 into RAM and flash
3 =
User1Save save actual parameter set form RAM into macro User1
4 =
User2Load load macro User2 into RAM and flash
5 =
User2Save save actual parameter set form RAM into macro User2
6 =
Standard load macro standard into RAM and flash
7 =
Man/Const load macro manual / constant speed into RAM and flash
8 =
Hand/Auto load macro hand (manual) / automatic into RAM and flash
9 =
Hand/MotPot load macro hand (manual) / motor potentiometer into RAM and flash
10 =
reserved
11 =
MotPot load macro motor potentiometer into RAM and flash
12 =
TorqCtrl load macro torque control into RAM and flash
13 =
TorqLimit load macro torque limit into RAM and flash
14 =
DemoStandard load macro demo standard into RAM and flash
15 =
2WreDCcontUS load macro 2 wire with US style DC-breaker into RAM and flash
16 =
3WreDCcontUS load macro 3 wire with US style DC-breaker into RAM and flash
17 =
3WreStandard load macro 3 wire standard into RAM and flash
Notes:
When loading a macro, group 99 is set / reset as well.
If User1 is active, AuxStatWord (8.02) bit 3 is set. If User2 is active, AuxStatWord (8.02) bit 4 is set.
It is possible to change all preset parameters of a loaded macro. On a macro change or an application
restore command of the actual macro the ma
cro depending parameters are restored to the macro’s default
values.
In case macro User1 or User2 is loaded by means of ParChange (10.10),
it is not saved into the flash and
thus not valid after the next power on.
Int. Scaling: 1 == 1 Type: C Volatile: Y
NotUsed
TorqCtrl
NotUsed
-
99.09 DeviceName (device name)
DeviceName (99.09)
is fixed set to DCS550 and cannot be changed.
Note:
This parameter is only visible if a SDCS
-COM-8 is connected.
Int. Scaling: 1 == 1 Type: C Volatile: N
DCS550
DCS550
DCS550
-
99.10 NomMainsVolt (nominal AC mains voltage)
Nominal mains voltage (AC) of the supply. The default and maximum values are preset automatically
according to
TypeCode (97.01).
Absolute max. is 525 V
Int. Scaling: 1 == 1 V Type: I Volatile: N
0
(97.01)
(97.01)
V
99.11 M1NomFldCur (nominal field current)
Nominal field current from the motor rating plate.
Int. Scaling: 100 == 1 A Type: I Volatile: N
0.3
35
0.3
A