Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
Signal / Parameter name
min.
max.
def.
unit
44.03 M1TiFex (i-part field current controller)
Integral time of the field current controller
. M1TiFex (44.03) defines the time within the integral part of the
controller achieves the same value as the proportional part.
Example:
The controller generates 15 % of motor nominal field current [
M1NomFldCur (99.11)] with M1KpFex (44.02) =
3, if the field current error is 5 % of
M1NomFldCur (99.11). On that condition and with M1TiFex (44.03) = 200
ms follows:
the controller generates 30 % of motor nominal field current, if the current error is constant, after 200 ms
are elapsed (15 % from proportional part and 15 % from integral part).
Setting
M1TiFex (44.03) to 0 ms disables the integral part of the field current controller and resets its
integrator.
Int. Scaling: 1 == 1 ms Type: I Volatile: N
0
64000
200
ms
44.04 M1FldHeatRef (field heating reference)
Field current reference
- in percent of M1NomFieldCur (99.11) - for field heating. Field heating is released
according to
FldHeatSel (21.18).
Int. Scaling: 1 == 1 % Type: I Volatile: N
0
100
100
%
44.05 - 44.06 Unused
44.07 EMF CtrlPosLim (positive limit EMF controller)
Positive limit for EMF controller in percent of nominal flux.
Int. Scaling: 1 == 1 % Type: I Volatile: N
0
100
10
%
44.08 EMF CtrlNegLim (negative limit EMF controller)
Negative limit for EMF controller in percent of nominal flux.
Int. Scaling: 1 == 1 % Type: I Volatile: N
-100
0
-100
%
44.09 KpEMF (p-part EMF controller)
Proportional gain of the EMF
controller.
Example:
The controller generates 15 % of motor nominal EMF with
KpEMF (44.09) = 3, if the EMF error is 5% of
M1NomVolt (99.02)
.
Int. Scaling: 100 == 1 Type: I Volatile: N
0
325
0.5
-
44.10 TiEMF (i-part EMF controller)
Integral
time of the EMF controller. TiEMF (44.10) defines the time within the integral part of the controller
achieves the same value as the proportional part.
Example:
The controller generates 15 % of motor nominal EMF with
KpEMF (44.09) = 3, if the EMF error is 5% of
M1NomVolt (99.02)
. On that condition and with TiEMF (44.10) = 20 ms follows:
the controller generates 30 % of motor nominal EMF, if the EMF error is constant, after 20 ms are elapsed
(15 % from proportional part and 15 % from integral part).
Setting
TiEMF (44.10) to 0 ms disables the integral part of the EMF controller and resets its integrator.
Int. Scaling: 1 == 1 ms Type: I Volatile: N
0
64000
50
ms
44.11 Unused
44.12 FldCurFlux40 (field current at 40% flux)
Field current
at 40 % flux in percent of M1NomFldCur (99.11).
Int. Scaling: 1 == 1 % Type: I Volatile: N
0
100
40
%
44.13 FldCurFlux70 (field current at 70% flux)
Field current at 70 % flux in percent of
M1NomFldCur (99.11).
Int. Scaling: 1 == 1 % Type: I Volatile: N
0
100
70
%
44.14 FldCurFlux90 (field current at 90% flux)
Field current at 90 % flux in percent of
M1NomFldCur (99.11).
Int. Scaling: 1 == 1 % Type: I Volatile: N
0
100
90
%
Group 45: Field converter settings