Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
44.03 M1TiFex (i-part field current controller)
Integral time of the field current controller
. M1TiFex (44.03) defines the time within the integral part of the
controller achieves the same value as the proportional part.
The controller generates 15 % of motor nominal field current [
M1NomFldCur (99.11)] with M1KpFex (44.02) =
3, if the field current error is 5 % of
M1NomFldCur (99.11). On that condition and with M1TiFex (44.03) = 200
the controller generates 30 % of motor nominal field current, if the current error is constant, after 200 ms
are elapsed (15 % from proportional part and 15 % from integral part).
M1TiFex (44.03) to 0 ms disables the integral part of the field current controller and resets its
Int. Scaling: 1 == 1 ms Type: I Volatile: N
44.04 M1FldHeatRef (field heating reference)
Field current reference
- in percent of M1NomFieldCur (99.11) - for field heating. Field heating is released
FldHeatSel (21.18).
Int. Scaling: 1 == 1 % Type: I Volatile: N
44.07 EMF CtrlPosLim (positive limit EMF controller)
Positive limit for EMF controller in percent of nominal flux.
Int. Scaling: 1 == 1 % Type: I Volatile: N
44.08 EMF CtrlNegLim (negative limit EMF controller)
Negative limit for EMF controller in percent of nominal flux.
Int. Scaling: 1 == 1 % Type: I Volatile: N
44.09 KpEMF (p-part EMF controller)
Proportional gain of the EMF
controller.
The controller generates 15 % of motor nominal EMF with
KpEMF (44.09) = 3, if the EMF error is 5% of
.
Int. Scaling: 100 == 1 Type: I Volatile: N
44.10 TiEMF (i-part EMF controller)
Integral
time of the EMF controller. TiEMF (44.10) defines the time within the integral part of the controller
achieves the same value as the proportional part.
The controller generates 15 % of motor nominal EMF with
KpEMF (44.09) = 3, if the EMF error is 5% of
. On that condition and with TiEMF (44.10) = 20 ms follows:
the controller generates 30 % of motor nominal EMF, if the EMF error is constant, after 20 ms are elapsed
(15 % from proportional part and 15 % from integral part).
TiEMF (44.10) to 0 ms disables the integral part of the EMF controller and resets its integrator.
Int. Scaling: 1 == 1 ms Type: I Volatile: N
44.12 FldCurFlux40 (field current at 40% flux)
Field current
at 40 % flux in percent of M1NomFldCur (99.11).
Int. Scaling: 1 == 1 % Type: I Volatile: N
44.13 FldCurFlux70 (field current at 70% flux)
Field current at 70 % flux in percent of
M1NomFldCur (99.11).
Int. Scaling: 1 == 1 % Type: I Volatile: N
44.14 FldCurFlux90 (field current at 90% flux)
Field current at 90 % flux in percent of
M1NomFldCur (99.11).
Int. Scaling: 1 == 1 % Type: I Volatile: N