EasyManua.ls Logo

ABB PFEA 112 - Input Buffer, Communication Block from PFEA112 to PLC; Output Buffer, Communication Block from PLC to PFEA112

ABB PFEA 112
216 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Tension Electronics PFEA111/112, User Manual
Section 3.13.5 Handling of Measurement Data through Profibus
3BSE029380R0101 Rev C 3-31
3.13.5.4 Input Buffer, Communication Block from PFEA112 to PLC
This section specifies measurement values and Boolean values in the input buffer
communication block.
Data:
Value 1, Web tension
Step response time (filtering) equal to the setting for voltage output, 16-bit, 2-complement
representation (Integer 16)
Value 2, Web tension
Step response time (filtering) equal to the setting for current output, 16-bit, 2-complement
representation (Integer 16)
Boolean in:
The error or warning is active when the corresponding bit is set to “1”.
Bit No. 0: Flash memory error
Bit No. 1: EEPROM error
Bit No. 2: Supply error
Bit No. 3: Load cell excitation error
Bit No. 4: Synchronization problem
3.13.5.5 Output Buffer, Communication Block from PLC to PFEA112
This section specifies Boolean values in the output buffer communication block.
Bit No. 0: Zero set. Zero set is performed when the bit is changed from “0” to “1”.
Data Byte No.
Bit No.
76543210
Value 1
01 MSB
02 LSB
Value 2
03 MSB
04 LSB
Boolean in 05 No. 7 No. 6 No. 5 No. 4 No. 3 No. 2 No. 1 No. 0
06 Spare for future use
Data Byte No.
Bit No.
76543210
Boolean out 01 No. 7 No. 6 No. 5 No. 4 No. 3 No. 2 No. 1 No. 0
02 Spare for future use

Table of Contents

Related product manuals