Tension Electronics PFEA111/112, User Manual
Section A.4 Factory Default Settings
3BSE029380R0101 Rev C A-7
A.4 Factory Default Settings
Table A-10. Factory Default Settings
PFEA111 PFEA112
Display language English English
Display unit NN
Set Decimals 00
Load cells per roll 22
Object type Standard roll Standard roll
Load cell nominal load 1.0 kN 225 lbs 1.0 kN 225 lbs
Wrap gain 11
Current output
Filter setting 250 ms 250 ms
High tension 2000 N 2000 N
High output 20.00 mA 20.00 mA
Low tension 0 N 0 N
Low output 4.00 mA 4.00 mA
High limit 21.00 mA 21.00 mA
Low limit 0.00 mA 0.00 mA
Voltage output
Filter setting 250 ms 250 ms
High tension 2000 N 2000 N
Low tension 0 N 0 N
High output +10.00 V +10.00 V
Low output 0.00 V 0.00 V
High limit +11.00 V +11.00 V
Low limit -5.00 V -5.00 V
Profibus -Off
Address - 126