6.11.2.4 Settings
Table 93: GOPPDOP (32) Group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Disable / Enable
OpMode1 Disabled
OverPower
- - OverPower Operation mode 1
Power1 0.0 - 500.0 % 0.1 1.0 Power setting for stage 1 in % of calculated
power base value
Angle1 -180.0 - 180.0 Deg 0.1 0.0 Characteristic angle for stage 1
TripDelay1 0.010 - 6000.000 s 0.001 1.000 Trip delay for stage 1
OpMode2 Disabled
OverPower
- - OverPower Operation mode 2
Power2 0.0 - 500.0 % 0.1 1.0 Power setting for stage 2 in % of calculated
power base value
Angle2 -180.0 - 180.0 Deg 0.1 0.0 Characteristic angle for stage 2
TripDelay2 0.010 - 6000.000 s 0.001 1.000 Trip delay for stage 2
Table 94: GOPPDOP (32) Group settings (advanced)
Name
Values (Range) Unit Step Default Description
k 0.00 - 0.99 - 0.01 0.00 Low pass filter coefficient for power
measurement, V and I
Table 95: GOPPDOP (32) Non group settings (basic)
Name
Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 6 - 1 1 Selection of one of the Global Base Value
groups
Mode A, B, C
Arone
Pos Seq
AB
BC
CA
A
B
C
- - Pos Seq Mode of measurement for current and voltage
1MRK 511 287-UUS A Section 6