Section 18 IED and functionality tests
18.1 Electromagnetic compatibility tests
Table 568: Electromagnetic compatibility tests
Description Type test value Reference
100 kHz and 1 MHz burst
disturbance test
IEC 61000-4-18, level 3
IEC 60255-22-1
ANSI C37.90.1-2012
Common mode
2.5 kV
Differential mode 2.5 kV
Electrostatic discharge test IEC 61000-4-2, level 4
IEC 60255-22-2
ANSI C37.90.3-2001
Contact discharge
8 kV
Air discharge 15 kV
Radio frequency interference
tests
Conducted, common mode 10 V (emf), f=150 kHz...80 MHz IEC 61000-4-6 , level 3
IEC 60255-22-6
Radiated, amplitude-
modulated
20 V/m (rms), f=80...1000 MHz
and f=1.4...2.7 GHz
IEC 61000-4-3, level 3
IEC 60255-22-3
ANSI C37.90.2-2004
Fast transient disturbance tests
IEC 61000-4-4
IEC 60255-22-4, class A
ANSI C37.90.1-2012
Communication ports
4 kV
Other ports 4 kV
Surge immunity test IEC 61000-4-5
IEC 60255-22-5
Communication 1 kV line-to-ground
Other ports 2 kV line-to-ground, 1 kV line-to-
line
Power supply 4 kV line-to-ground, 2 kV line-to-
line
Table continues on next page
1MRK 511 287-UUS A Section 18
IED and functionality tests
651