EasyManua.ls Logo

ABB REC650 ANSI - Enclosure Class

ABB REC650 ANSI
700 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 561: IRIG-B
Type Value Accuracy
Input impedance 430 Ohm -
Minimum input voltage
HIGH
4.3 V -
Maximum input voltage
LOW
0.8 V -
Table 562: EIA-485 interface
Type Value Conditions
Minimum differential
driver output voltage
1.5 V
Maximum output current 60 mA -
Minimum differential
receiver input voltage
0.2 V -
Supported bit rates 300, 600, 1200, 2400,
4800, 9600, 19200,
38400, 57600, 115200
-
Maximum number of 650
IEDs supported on the
same bus
32
-
Max. cable length 925 m (3000 ft) Cable: AWG24 or better, stub lines shall be avoided
Table 563: Serial rear interface
Type
Counter connector
Serial port (X9) Optical serial port, type ST for IEC 60870-5-103 and
DNP serial
Table 564: Optical serial port (X9)
Wave length
Fibre type Connector
Permitted path attenuation
1)
820 nm MM 62,5/125 µm
glass fibre core
ST 6.8 dB (approx. 1700m length with 4 db /
km fibre attenuation)
820 nm MM 50/125 µm
glass fibre core
ST 2.4 dB (approx. 600m length with 4 db / km
fibre attenuation)
1) Maximum allowed attenuation caused by fibre
17.8 Enclosure class