6.11.3.3 Signals
Table 97: GUPPDUP (37) Input signals
Name
Type Default Description
I3P GROUP
SIGNAL
- Three phase group signal for current inputs
V3P GROUP
SIGNAL
- Three phase group signal for voltage inputs
BLOCK BOOLEAN 0 Block of function
BLK1 BOOLEAN 0 Block of step 1
BLK2 BOOLEAN 0 Block of step 2
Table 98: GUPPDUP (37) Output signals
Name Type Description
TRIP BOOLEAN Common trip signal
TRIP1 BOOLEAN Trip signal from stage 1
TRIP2 BOOLEAN Trip signal from stage 2
BFI_3P BOOLEAN General pickup signal
PICKUP1 BOOLEAN Pickup signal from stage 1
PICKUP2 BOOLEAN Pickup signal from stage 2
P REAL Active Power
PPERCENT REAL Active power in % of calculated power base value
Q REAL Reactive power
QPERCENT REAL Reactive power in % of calculated power base value
6.11.3.4 Settings
Table 99: GUPPDUP (37) Group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Disable / Enable
OpMode1 Disabled
UnderPower
- - UnderPower Operation mode 1
Power1 0.0 - 500.0 % 0.1 1.0 Power setting for stage 1 in % of calculated
power base value
Angle1 -180.0 - 180.0 Deg 0.1 0.0 Characteristic angle for stage 1
TripDelay1 0.010 - 6000.000 s 0.001 1.000 Trip delay for stage 1
OpMode2 Disabled
UnderPower
- - UnderPower Operation mode 2
Table continues on next page
1MRK 511 287-UUS A Section 6
Current protection
157
Technical manual